Extension cords, Symbology – Harbor Freight Tools 93213 User Manual

Page 6

Advertising
background image

Page 6

For technical questions, please call 1-800-444-3353.

SKU 93213

Extension Cords

Grounded

1.

tools require a three wire

extension cord. Double Insulated

tools can use either a two or three wire

extension cord.
As the distance from the supply outlet

2.

increases, you must use a heavier gauge

extension cord. Using extension cords

with inadequately sized wire causes a

serious drop in voltage, resulting in loss

of power and possible tool damage.

(See Table A.)
The smaller the gauge number of the

3.

wire, the greater the capacity of the cord.

For example, a 14 gauge cord can carry

a higher current than a 16 gauge cord.

(See Table A.)
When using more than one extension

4.

cord to make up the total length, make

sure each cord contains at least the

minimum wire size required.

(See Table A.)
If you are using one extension cord for

5.

more than one tool, add the nameplate

amperes and use the sum to determine

the required minimum cord size.

(See Table A.)
If you are using an extension cord

6.

outdoors, make sure it is marked with the

suffix “W-A” (“W” in Canada) to indicate it

is acceptable for outdoor use.
Make sure the extension cord is properly

7.

wired and in good electrical condition.

Always replace a damaged extension

cord or have it repaired by a qualified

electrician before using it.
Protect the extension cords from sharp

8.

objects, excessive heat, and damp or

wet areas.

RECOMMENdEd MINIMuM WIRE gAugE

FOR EXTENSION CORdS*

(120/240 VOLT)

NAMEPLATE

AMPERES

(at full load)

EXTENSION CORd

LENgTH

25’

50’

75’

100’

150’

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

TABLE A

* Based on limiting the line

voltage drop to five volts at

150% of the rated amperes.

Symbology

Double Insulated

Canadian Standards Association

Underwriters Laboratories, Inc.

V~

Volts Alternating Current

A

Amperes

n0 xxxx/min.

No Load Revolutions per Minute

(RPM)

Advertising