Chromalox PK410-1 User Manual

Installation instructions, Type wr room thermostat, Pk410-1

Advertising
background image

PK410-1

161-048634-001

JUNE, 1989

4WR

Installation Instructions

(Supersedes PK410)

Type WR Room Thermostat

© 2010 Chromalox, Inc.

Specifications – Table A

GENERAL

Positive accuracy, long and reliable service, 3° differential.

Heavy-duty, single stage, SPST line voltage snap-acting switch.
Patented hydraulic element. WR-80 has internal sensing element
and thermometer on cover; WR-90 has external, coiled sensing
element but no thermometer. Both have a low position which
drops control point to keep heater off. WR-80 and WR-90 fin-
ished in tough metallic gray with chrome trim; mounting plate
fits outlet or conduit box.
Uses – Automatically controls room temperature by turning elec-
tric air heaters on and off. Can be used to control the air heaters
directly, within thermostat rating. For higher ratings use thermo-
stat with magnetic contactor. Place thermostat on inside wall,
away from undue heating or cooling influences, about 4 feet
above the floor. WR-90 is especially useful in holding lower tem-
peratures, for example, in garages, warehouses, factories, etc.

NOTICE: Type WR thermostats are designed for temperature
control service only. Because they do not fail safe, they should
not be used for temperature limiting duty.
CAUTION: Users should install adequate back-up controls and
safety devices with their electric heating equipment. Where the
consequences of failure may be severe, back-up controls are
essential. Although the safety of the installation is the responsi-
bility of the user, Chromalox will be glad to make equipment rec-
ommendations.
Principle of Operation – Control action of these thermostats is
provided through the principle of liquid volume change. With a
variation in temperature, the liquid in the sensing element
expands or contracts, causing a bellows to actuate the switching
mechanism.

CAUTION: Not for use in hazardous environments
as described in National Electrical Code. Failure to
comply can result in explosion or fire.

WR-80

40 to 80°F

UL Listed

Maximum Rating

Range

Model

(°F)

120Vac

† 115Vac

240Vac

† 230Vac

277Vac

480Vac

WR-80

40-80

125va pilot

125va pilot

125va pilot

25 amps

duty (use

22 amps

duty (use

18 amps

duty (use

WR-90

20-90

or 3000

with d-c

or 5280

with d-c

or 5000

with a-c

total watts

contactor)

total watts

contactor)

total watts

contactor)

WR-90

20 to 90°F

UL Listed

† d-c ratings not UL listed

5

3

/

8

2

1

/

2

2

1

/

4

2

9

/

16

6”

2

3

/

4

2

1

/

2

Note
WR-80 is
not a
Fail-Safe
Device.

Advertising