WIRING

Low-vo(tage power supply
600 V AC or less

-Sh

Low-voltage

Contractor

I Ì I a I 3 I 4 15 [ 5 I 7 f

2E Relay

^Stop

Start

Higti-voltaga power supply PT w control transformer

2.AKV—13.8K\/ AC

/[100~t20V Sacondaiy)

iJ\Operatìng

Xoil

L/

Control

Tsrminal

Numbers

High

voltage

CT

(Notes)

I WOTOn

"Connections of control power source

AC 100-120V—Terminals 1-2
AC 200-240V—Terminals 1-3

For other voit., use CPT.

"‘Connections of output contacts

NC“Oontact {opened when the 2E

Relay operated)—Terminals 8-9
NO-contact (closed when the 2E
Relay operated)—Terminals 9-10

“‘Connections of Remote reset switch

LOW-VOLTAGE

|_High-vortag©__
^ contactor

i|i

^ stop

^ Start
15 Operating
' Coll

l|2[3М4|5М6|7|a|9|To

I

2

£

Relay

b

a

o

P\

Hlgh“V

0ita9& CT sscondar/ circuit

wires pass through the windows of
the built-in CT's,

HIGH-VOLTAGE

HOW TO SET

Selection of the suitable model may require some preli­
minary calculations. See “Current Setting” to determine
if the calculated “Current Setting %” can be obtained

with the selected model given the motor full load current

(FLA). Model Selection can also be influenced by wire
size which limits the number of turns that can be passed
through the CT windows.

(1) Current Setting

(2E AT Rating)X(External CT Ratio)

N{g-i------------------------- ----------------------------

N(T) = Number of wire turns through 2E built-in CTs,

round off to nearest integer.

/m

. 0

4

*-

FLAxNxIOO

® "^9

0

) ^

2

^ yjj p

3

(jpg| ^ (External CT Ratio)

Notes: * Select the external CT ratio so that the current

setting % is as close to 100% as possible.

If no external CT are used, substitute with

1

.

0

” .

**For 1.15 Service Factor Motors. If the motor

has a 1.0 S.F. multiply the calculated “Current

Setting %” by 0,93, (Practice in USA)

Example: 200HP, 460V, 240A Full Load. 1.15 S.F.

Across-the-line start.
240 Amps exceeds the highest rated 2E

Relay, therefore, external CT’s must be
used, and the HPIY, 7 AT rated 2E, will be

chosen as the standard model when the
current exceeds the HP3Y’s rating. If 300/5

CT’s are used,

41, m 4 0,4-

n/ 240xNfT)x100%

the Current Setting % =---------------------------

7x(M0)

5

"'

= N01x57.14%.

And if 2 turns through the 2E Relay’s CT
windows (from the external CT’s) are used,
the % Dial

Setting = 2x57.14=114% = 110% or 115%

(2) Time setting

Determine the protection curve from 2E Relay

operating curves, and read the operating time at 600%
of setting current. Adjust the time setting dip switch
to the nearest setting above the operating time.