Chapter 6. connecting devices, Devices – Comtrol IOLM 4-EIP User Manual
Page 45

IO-Link Master 4-EIP User Guide: 2000582 Rev. A
Chapter 6. Connecting Devices - 45
Chapter 6. Connecting Devices
The IO-Link Master provides four IO-Link ports with M12 connectors (5-pin female/A
coded).
Note: Make sure that you tighten the cables properly to maintain IP67 capabilities.
This table provides signal information for the IO-Link connectors.
This table provides information that you may need regarding the IO-Link connectors.
Note: IO-Link ports must have an approved cable or protective cover attached to the port guarantee IP67
compliance.
Pin
Signal
Description
1
L+
Power supply (+)
2
DI
Digital input
3
L-
Power supply (-)
4
C/Q
Communication signal, which supports
SDCI (IO-Link) or SIO (standard input/
output)
5
N/A
Not connected
Current and Power
Value
Maximum IO-Link Supply
200mA
Maximum C/Q Current:
High
Low
200mA
200mA
Peak C/Q Current:
High
Low
500mA
500mA
C/Q & DI Input:
Maximum
Minimum
Power Input +0.5VDC
-0.5VDC
SDCI (IO-Link) Transmission Rates:
COM1
COM2
COM3
4.8Kbps
38.4Kbps
230.4Kbps