Eagle Microsystems LP4300 User Manual

Page 6

Advertising
background image

4.2 Checking the load cells.

1. Load Cell resistance test:

a.

Disconnect the load cells from the Summing Box and measure the resistance as shown in

Figure 3.

b. Any electrical leakage between the leads and the load cell case is usually caused by moisture
leakage into the load cell or by moisture in a damaged load cell cable.

c. If a load cell does not pass the above resistance tests, replace it with a known good one.

RED TO BLACK

360

GREEN TO WHITE

350 +/- 5

RED, BLACK, GREEN,

WHITE, OR YELLOW

GREATER THAN 200

TO CASE

MEGOHMS *

* Using a portable Ohm meter on highest range you should read infinity

LOAD CELL WIRING

BLK -EXT

GRN +SIG

RED +EXT

YEL SHLD

WHT -SIG

LOAD
CELL

LOAD CELL RESISTANCE CHECK

FIGURE 3

2. Load Cell zero shift test:

a.

Remove all the weight from the load cell and measure the output as shown in

Figure 4.

b. Connect a DC power supply of 10 or 15 volts to the Red (+) and Black (-) excitation load cell
leads.

c.

The measured output between the Green (+) and White (-) signal leads should be less

than 5 millivolts.

d. An output signal greater than 5 millivolts indicates a zero shift caused by mechanical
overload.

e. If the output signal is between 5 and 15 millivolts, the load cells zero has shifted but will
probably still continue to work.

f.

If the output signal is greater than 15 millivolts, the load cell should be replaced with a

known good one.

Advertising