Operating instructions – ebm-papst D3G283-AB37-01 User Manual
Page 8

Operating instructions
D3G283-AB37-01
Translation of the original operating instructions
4.5 Connection screen
No.
Conn.
Designation
Colour
Function / assignment
1
1, 2
PE
green/
yellow
Protective earth
1
3, 4, 5
L1, L2, L3
black
Supply voltage 50 / 60 Hz
1
6
COM
white 1
Floating status contact, break for failure (2 A, max. 250 VAC, min. 10 mA, AC1)
1
7
NC
white 2
Floating status message contact, break for failure
2
8
0 - 10 V
yellow
Control input, set value 0 - 10 VDC, impedance 100 kOhm, SELV
2
11
+ 10 V
red
Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for ext. devices (e.g. potentiometer),
SELV
2
12
GND
blue
Reference mass for control interface, SELV
Item no. 50383-5-9970 · Revision 82547 · Release 2014-05-08 · Page 8 / 11