Operating instructions

A3G560-AP68-23

Translation of the original operating instructions

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

; Check whether the data on the type plate agree with the connection

data.

; Before connecting the device, ensure that the supply voltage matches

the operating voltage of the device.

; Only use cables designed for current according to the type plate.

For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

Earth wire contact resistance to EN 61800-5-1
Compliance with the impedance specifications to EN 61800-5-1 for the
protective earth circuit must be verified in the end application.
Depending on the installation situation, it may be necessary to install an
additional protective earthing conductor via the additional protective earth
connection point available on the device.
The protective earth connection point is located on the housing and has
a protective earth symbol and a bore hole.

4.2.2 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

The values lie in a range of typical < 250 mA.

The effective power in this operating state (readiness for operation) is
simultaneously at typical < 4 W.

4.2.3 Residual current operated device

Only universal (type B or B+) RCD protective devices are
permitted. Like frequency inverters, RCD protective devices
cannot provide personal safety while operating the device.
When switching on the power supply of the device, pulsed
charge currents from the capacitors in the integrated EMC filter
can lead to the RCD protective devices triggering without
delay. We recommend residual current devices with a trigger
threshold of 300 mA and delayed triggering (super-resistant,
characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Factory settings

Factory settings with which the device is pre-set by ebm-papst.

Operation mode

PWM controlling

Group adress

01

Fan / device adress

01

Max. PWM / %

100

Min. PWM / %

0

Save set value to
EEPROM

No

Set value control

Analog

Control function

Positive (heating)

Item no. 50608-5-9970 · Revision 82547 · Release 2014-05-08 · Page 7 / 11