Operating instructions – ebm-papst A3G800-AO84-01 User Manual

Page 8

Advertising
background image

Operating instructions

A3G800-AO84-01

Translation of the original operating instructions

4.4 Connection screen

No.

Conn.

Designation

Colour

Function / assignment

1

1

PE

green/
yellow

Ground wire

1

3

L1

black

Supply voltage, 50/60 Hz

1

4

L2

black

Supply voltage, 50/60 Hz

1

5

L3

black

Supply voltage, 50/60 Hz

1

6

COM

white 1

Floating status message contact, normally closed connection (2 A, max. 250 VAC, min. 10 mA,
AC1)

1

7

NC

white 2

Floating status message contact, normally closed connection

2

8

0-10 V

yellow

Control input, set value 0-10 VDC, impedance 100 kΩ, SELV

2

10

P

orange

Do not use

2

11

+10 V

red

Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for external devices (e.g.
potentiometer), SELV

2

12

GND

blue

Reference mass for control interface, SELV

Item no. 50187-5-9970 · Revision 82547 · Release 2014-05-08 · Page 8 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Advertising