MAC 10 LE-AC SERVICE MANUAL

7

E

G

A

P

4 SERVICE: Removal and Replacement of the HEPA/ULPA

Filter (Standard Unit)

WARNING!

Disconnect the unit from the electrical power source before attempting any

service.

WARNING!

The Standard Filter is protected with an expanded metal face screen. This is

never to be used to handle the filter. It is only for protection against an accidental

touch of the filter. Only handle the filter by the frame.

Tools Required:

Phillips Head Driver, Battery Operated Drill with a 5/32 Drill

Bit, Rivet Hand Tool, Ø5/32 aluminum rivet grip range .126-

.187

Step 1. Remove unit from ceiling.

Step 2. Remove the 10 screws holding the HEPA/ULPA filter to the lid assembly.

Step 3. Lift the lid assembly off the HEPA/ULPA filter (see Figure 3). Remove Filter

deflectors using 5/32 drill bit. Keep filter deflectors to install in new filter.

Discard the used filter as per requirements of the applicable regulations.

Carefully install the filter deflectors into the new filter using the 5/32 rivets. Do

not touch or place the filter deflectors on the HEPA/ULPA media pack. This

could cause tears in the filter pack.

Note: Before replacing with a new HEPA/ULPA filter, carefully inspect the new filter for

any visible damage. Also inspect the gasket in the “tee” bar to insure a tight seal.

Replace as necessary.

Step 4. Replace with the new HEPA/ULPA filter and assemble by reversing the above

steps.

Figure 4 – Standard Filter Replacement

Lid Screw (10)

HEPA/ULPA

Filter

Lid Assembly

ON/OFF

Switch

#8 SCREWS (10X)

Ø5/32 RIVET (6X)

FILTER DEFLECTOR

Speed Control