EVCO EVRSF205N9VRB User Manual
Page 3

EVCO S.p.A. | Codice 104RSF200E124 | Page 3 of 8 | PT 20/14 | version 1.1
7.
Press and release the key: the display will show the
alarm selected (in the example “AH”).
To exit the procedure:
8.
Exit the information sequence.
9.1 Press and release the or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
9.2 Press and release the key.
6.3
Cancelling the HACCP alarm list
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Hold the key for 1 s: the display will show the first
label available.
3.
Press and release the or key to select “rLS”.
4.
Press and release the key.
5.
Press and release the
or
key within
15 s to set “149”.
6.
Press and release the
key or do not operate for
15 sec: the display will show a flashing “- - - -” for
4 sec and the “HACCP” LED switches off, after which
the device will exit the procedure.
If the device does not have any alarms stored, the label
“rLS” will not be displayed.
7
COMPRESSOR OPERATING HOURS COUNT
7.1
Preliminary notes
The device can memorise up to 9.990 compressor operating
hours.
The parameter C10 establishes the number of operating
hours is higher than the limit at which the need for mainte-
nance is signalled.
7.2
Display of Compressor Operation Hours
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Hold the key for 1 s: the display will show the first
label available.
3.
Press and release the key or the key to select “CH”.
4.
Press and release the key.
To exit the procedure:
5.
Press and release the
key or do not operate for
60 sec.
6.1 Press and release the or key until the display
shows the cell temperature or do not operate for 60
sec.
Alternatively:
6.2 Press and release the key.
7.3
Cancelling the HACCP alarm list
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Hold the key for 1 s: the display will show the first
label available.
3.
Press and release the or key to select “rCH”.
4.
Press and release the key.
5.
Press and release the
or
key within
15 s to set “149”.
6.
Press and release the
key or do not operate for
15 sec: the display will show “- - -” flashing for
4 sec, after which the device will exit the procedure.
8
SYNCHRONISATION OF DEFROSTING PERI-
ODS (ONLY IF PARAMETER i0 AND/OR PA-
RAMETER i5 IS SET AT 6)
8.1
Preliminary notes
The activation of defrosting causes the activation of
the digital input (at maximum for the time established
w i t h p a r a m e t e r d 2 4 o r u n t i l t h e c o n c l u s i o n o f
predripping).
If the digital input is connected in parallel to the digital input
of other devices configured in the same way, the activation
of the input caused the activation of defrosting in the other
devices.
The devices start dripping simultaneously with the con-
clusion of the predripping of the last device to end the
same.
9
SETTINGS
9.1
Setting the working setpoint
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Press and release the
key: the
LED will flash.
3.
Press and release the
or
key within
15 sec; see also parameters r1, r2 and r3
4.
Press and release the
key or do not operate for
15 sec: the LED will switch off and then the device
will exit the procedure.
To exit the procedure before the operation is complete:
5.
Do not operate for 15 sec (any changes will be saved).
The working setpoint can also be set via parameter
SP.
9.2
Setting the configuration parameters
To begin the procedure:
1.
Make sure no procedures are in progress
2.
Hold the and keys down for 4s:the display will
show “PA”.
3.
Press and release the key.
4.
Press and release the
or
key within
15 s to set “-19”.
5.
Press and release the
key or do not operate for
15 sec.
6.
Hold the
and
keys down for 4 s:
the display will show “SP”.
To select a parameter:
7.
Press and release the
or key.
To change a parameter:
8.
Press and release the key.
9.
Press and release the
or
key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and keys for 4 sec and do not
operate for 60 sec (any changes will be saved).
After changing the parameters, suspend power supply flow
to the device.
9.3
Restoring the Manufacturer’s Settings
To begin the procedure:
1.
Make sure no procedures are in progress
2.
Hold the
and
keys down for 4 s:
the display will show “PA”.
3.
Press and release the key.
4.
Press and release the
or
key within
15 s to set “149”.
5.
Press and release the
key or do not operate for
15 sec.
6.
Hold the
and
keys down for 4 s:
the display will show “dEF”.
7.
Press and release the key.
8.
Press and release the
or
key within
15 s to set “1”.
9.
Press and release the
key or do not operate for
15 sec: the display will show “dEF” flashing for
4 sec, after which the device will exit the proce-
dure.
10. Cut the device power supply off.
To exit the procedure before the operation is complete:
11. Hold the and key down for 4 s during the proce-
d u r e ( i . e . b e f o r e s e t t i n g “ 1” :
Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate
(see chapter 14).
10
WARNING LIGHTS AND DIRECTIONS
10.1
Signals
LED
Part
compressor LED light
if the LED is on, then the compressor is on
if the LED is flashing:
-
the working setpoint is in the process of being
changed (via the procedure described in para-
graph 9.1)
-
a compressor protection will be in progress;
see parameters C0, C1, C2, C14, C15, C16
and i7
Defrost LED
If it is on:
-
defrosting is in progress
-
predripping will be in progress; see parameter
d16
if the LED is flashing:
-
defrosting will be requested but a compressor
protection will be in progress; see the param-
eters C0, C1 and C2
-
dripping will be in progress; see parameter
d7
-
the refrigerant fluid heating will be in progress;
see parameter d15
Evaporator fan LED light
If it is on:
-
the evaporator fan will be on
if the LED is flashing:
-
evaporator fan standstill will be in progress;
see parameter F3
AUX Auxiliary LED
If it is on:
-
the cell light will have been switched on in
manual mode (only if parameter u1 and/or
parameter u11 is set at 0)
-
the demister resistors will be switched on (only
if the parameter u1 and/or parameter u11 is
set at 1)
-
the auxiliary output will have been switched
on in manual mode (only if parameter u1
and/or parameter u11 is set at 2)
-
the door resistors will be switched on (only
and provided parameter u1 and/or parameter
u11 is set at 4)
-
the neutral area operating resistors will be
activated (only if parameter u1 and/or pa-
rameter u11 is set at 5)
-
the condenser fan will be on (only if param-
eter u1 and/or parameter u11 is set at 6)
if the LED is flashing:
-
the cell light will have been switched on in
remote mode; see parameters i0 and i5 (only
if parameter u1 and/or parameter u11 is set
at 0)
-
the auxiliary output will have been switched
on in remote mode; see parameters i0 and i5
(only if parameter u1 and/or parameter u11
is set at 1)
-
condenser fan switch-off delay will be in
progress; see parameter F12 (only if param-
eter u1 and/or parameter u11 is set at 6)
HACCP HACCP LED
if it is on, all information regarding HACCP alarms
has not been displayed
if it is flashing, the device has stored at least one
new HACCP alarm
if it is off, all information regarding the HACCP
alarms has been displayed or the list of alarms has
been cancelled
maintenance LED
if on, compressor maintenance will be requested;
see parameter C10
“overcooling” LED
if it is on, the “overcooling” function will be in
function; see parameters r5 and r6
°C
degree Celsius LED
if on, the temperatures will be displayed using the
degree Celsius grade unit of measurement; see
parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)
°F
degree Fahrenheit LED
if on, the temperatures will be displayed using the
degree Fahrenheit grade unit of measurement;
see parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)
On/stand-by LED
if it is on, the device will be off (
“stand-by” state)
if it is off, the device will be on (“on” state)
10.2
Signal Descriptions/Explanations
Code Part
rhL
operation for a low percentage of relative humidity
in progress
rhH
operation for a high percentage of relative humid-
ity in progress
Loc
the keyboard is blocked; see paragraph 3.11
the work setpoint is blocked; see parameter r3
- - -
the operation requested is not available
11
ALARMS
11.1
Alarms
Code Part
AL
Minimum alarm temperatures (HACCP alarms)
Solutions:
-
check the temperature associated to the
alarm; see parameters A0, A1 and A2
Main consequences:
-
if parameter A0 is set at 0, the device will
store the alarm
-
the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)
AH
Maximum temperature alarm (HACCP alarms)
Solutions:
-
check the cell temperature; see parameters
A4 and A5
Main consequences:
-
the device will memorise the alarm
-
the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)