2 alarm off status, 3 unit type – EVCO EPK4BHQ1AH Installer manual User Manual

Page 46

Advertising
background image

EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 46 of 114

6.2

Alarm OFF status

When the machine is turned on an additional status, OFF from alarm (Alarm Off) exists. This shuts down the unit,

all devices, and closes the external air shutters completely until the alarm conditions are restored.

The central alarm will shut down to OFF status if there is no digital / supervisor consent or shut down is requested via

the keyboard. The alarms which provoke this status are as follows:

-

Fan alarms

-

Air Flow Meter alarm

-

Fire/smoke alarm

Once alarm conditions have been restored the machine will return to normal operation.

6.3

Unit type

While the machine is turned off, using the parameter PG00 in the CONFIGURATION Menu, it is possible to choose the

type of unit that you wish to utilize. Based on the value of the parameters, different defaults become available for the

positioning of inputs and outputs.

The control and other parameters which correspond to functionalities can be modified manually according to user

requirements. The machines and their configurations are described graphically in the next paragraphs.


Note:

the default configurations can also be modified according to user requirements by entering modifications to

the parameters manually.

CAUTION!

If the type of machine is changed (modifying the parameter PG00), the controller must successively be switched off

and back on again, in order to allow correct reconfiguration of the same. Moreover, it is advised to wait for a few

moments (approx 3 seconds) to assign all parameters that have been modified.