C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 24

MCCT thermal power plant controller settings:
Below find the settings to make on the MCCT regulator to make Vgraph a private zone terminal:
From the Installer

General parameters menu, disable the presence of the public V-graph display

via Enab. V-GRAPH parameter.

MCZN zone controllers settings:
Below find the settings to make on the MCZN regulators to make Vgraph a private zone terminal:
From the Installer

General parameters menu, enable the presence of the private zone V-graph

display by setting the V-GRAPH mode parameter in A+B.