3.6

Electrical characteristics

CPU

Microcontroller

8 bit

Program flash

128kB

Data memory RAM

4kB

EEPROM

4kB

A/D

8 channels at 10 bits

Power supply

Voltage

24 VAC / 20 … 60 VDC

Range

-10% +15%

Frequency

50/60 Hz / DC

Maximum absorbed input power

10 VA

Protection fuse

External

Digital outputs

Number

7

Type

Electromechanical relays

Maximum breaker current at 250 VAC 8 A

Operation cycle number

100,000

Minimum time between switching

20 s

Type of micro-interruption action

1C

Insulation between relays and low
voltage

Reinforced

Insulation between relays

Functional

Insulation between the relays and DO7 Reinforced

Digital outputs

Number

2

Type

SSR

Maximum breaker current at 48 VDC

80 mA

Please note: as an alternative to relay
outputs 5 and 6

Digital inputs

Number

7

Type

Clean contact

Current over contact closing to ground 2 mA

Maximum closing resistance

100Ω

OFF to ON detection time

100 ms

ON to OFF detection time

100 ms

Analogue inputs for

Number

3

NTC probes

Type

NTC (10KΩ ±1% @25

°

C)

NTC measurement range

-40

°

C - 100

°

C

NTC measurement accuracy

±1

°

C

NTC measurement sensitivity

0.1

°

C

Analogue inputs for

Number

2

NTC probes or pressure

Type

NTC (10KΩ ±1% @25

°

C)

transducers

NTC measurement range

-40

°

C – 100°C

NTC measurement accuracy

±1

°

C

NTC measurement sensitivity

0.1

°

C

Type

Current

Current measurement range

0/4

÷

20 mA

Current measurement accuracy

±0.08 mA