6 electrical characteristics – EVCO c-pro kilo User Manual
Page 19

C-PRO KILO HARDWARE MANUAL
Page 19
3.6
Electrical characteristics
CPU
Microcontroller
8 bit
Program flash
128kB
Data memory RAM
4kB
EEPROM
4kB
A/D
8 channels at 10 bits
Power supply
Voltage
24 VAC / 20 … 60 VDC
Range
-10% +15%
Frequency
50/60 Hz / DC
Maximum absorbed input power
10 VA
Protection fuse
External
Digital outputs
Number
7
Type
Electromechanical relays
Maximum breaker current at 250 VAC 8 A
Operation cycle number
100,000
Minimum time between switching
20 s
Type of micro-interruption action
1C
Insulation between relays and low
voltage
Reinforced
Insulation between relays
Functional
Insulation between the relays and DO7 Reinforced
Digital outputs
Number
2
Type
SSR
Maximum breaker current at 48 VDC
80 mA
Please note: as an alternative to relay
outputs 5 and 6
Digital inputs
Number
7
Type
Clean contact
Current over contact closing to ground 2 mA
Maximum closing resistance
100Ω
OFF to ON detection time
100 ms
ON to OFF detection time
100 ms
Analogue inputs for
Number
3
NTC probes
Type
NTC (10KΩ ±1% @25
°
C)
NTC measurement range
-40
°
C - 100
°
C
NTC measurement accuracy
±1
°
C
NTC measurement sensitivity
0.1
°
C
Analogue inputs for
Number
2
NTC probes or pressure
Type
NTC (10KΩ ±1% @25
°
C)
transducers
NTC measurement range
-40
°
C – 100°C
NTC measurement accuracy
±1
°
C
NTC measurement sensitivity
0.1
°
C
Type
Current
Current measurement range
0/4
÷
20 mA
Current measurement accuracy
±0.08 mA