Alarms Table
A list of all the alarms that are managed by the application is given below. The order of presentation is the same
as the order with which the alarms present themselves when they are active.
Code
Description of the alarms
Type
Consequence
Notes
EN01
Communication expansion error
Auto
Visualization
Delay able to be set
ES01
Suction probe C1 broken or disconnected
Auto
- Num. comp. ON
able to be set
- Inverter forced to
100% (if required and
if the only compressor
in the circuit)
Delay able to be set
ES02
Discharge probe C1 broken or disconnected
Auto
- Num. fan ON able to
be set
- Inverter forced to
100% (if required and
if the only fan in the
circuit)
- OFF throttling HP
circuit 1 (if enabled)
Delay able to be set
ES03
Suction probe C2 broken or disconnected
Auto
- Num. comp. ON
able to be set
- Inverter forced to
100% (if required and
if the only compressor
in the circuit)
Delay able to be set
ES04
Discharge probe C2 broken or disconnected
Auto
- Num. fan ON able to
be set
- Inverter forced to
100% (if required and
if the only fan in the
circuit)
- OFF throttling HP
circuit 2 (if enabled)
Delay able to be set
AC21
Thermal compressor 1
Set
OFF comp. 1
Delay able to be set
AC22
Thermal compressor 2
Set
OFF comp. 2
Delay able to be set
AC23
Thermal compressor 3
Set
OFF comp. 3
Delay able to be set
AC24
Thermal compressor 4
Set
OFF comp. 4
Delay able to be set
AC01
Hours of operation compressor 1
Auto
Visualization
AC02
Hours of operation compressor 2
Auto
Visualization
AC03
Hours of operation compressor 3
Auto
Visualization
AC04
Hours of operation compressor 4
Auto
Visualization
AF21
Thermal fan 1
Set
OFF fan 1
AF22
Thermal fan 2
Set
OFF fan 2
AF23
Thermal fan 3
Set
OFF fan 3
AF24
Thermal fan 4
Set
OFF fan 4
AF01
Hours of operation fan 1
Auto
Visualization
AF02
Hours of operation fan 2
Auto
Visualization
AF03
Hours of operation fan 3
Auto
Visualization
AF04
Hours of operation fan 4
Auto
Visualization
AL31
High discharge pressure C1
Auto
ON all fans
AL36
High suction pressure C1
Auto
ON all comp.
Delay able to be set
AL41
Low discharge pressure C1
Auto
OFF all fans
Delay able to be set *
AL46
Low suction pressure C1
Auto
OFF all comp.
Delay able to be set *
AL11
High discharge pressure pressure regulator C1
Set
OFF all comp.
AL21
Low suction pressure pressure regulator C1
Auto
OFF all comp.
Delay able to be set *
AL61
Liquid level C1
Manu
Visualization
Delay able to be set
ACC1
Common oil differential C1
Set
Visualization
Delay able to be set
AFC1
Common thermal fans C1
Set
Visualization