Configurability, Signals and alarms, Technical data – EVCO EC3L20 User Manual

Page 2: How to order

Advertising
background image

ADDITIONAL INFORMATIONS
-

for the whole period of a corrupted memory data alarm the access to the configura-

tion parameters setting procedure is refused

-

the modification of a parameter value which unit of measure is the hour or the

minute or the second has not immediate effect; to obtain this effect it must not be

executed during the course of the value

-

the configuration parameters values get stored in a non volatile memory even if a

lack of power supply happens.

CONFIGURABILITY

WORKING SETPOINT
LABELMIN. MAX. U.M. ST.

WORKING SETPOINT

r1

r2

°

C

0

working setpoint

It establishes the temperature associated to the output K 1.

CONFIGURATION PARAMETERS
LABEL MIN. MAX. U.M. ST.

MEASURE INPUT

/1

-15

+15

°

C

0

calibration

It establishes a threshold to add algebraically to the signal coming from the measure input (for

instance to correct the signal).
LABEL MIN. MAX. U.M. ST.

ON-OFF TEMPERATURE REGULATOR ASSOCIATED TO THE

WORKING SETPOINT AND TO THE OUTPUT K 1

r0

+1

+15

°

C

+2

hysteresis (differential)

It establishes the hysteresis (differential) relative to the working setpoint.
r1

-40

+99

°

C

-40

minimum working setpoint programmable

It establishes the minimum working setpoint programmable; the instrument automatically veri-

fies if the value established with the parameter r1 is below the maximum working setpoint

programmable established with the parameter r2.
r2

-40

+99

°

C

+99

maximum working setpoint programmable

It establishes the maximum working setpoint programmable; the instrument automatically

verifies if the value established with the parameter r2 is above the minimum working setpoint

programmable established with the parameter r1.
LABEL MIN. MAX. U.M. ST.

OUTPUT K 1 PROTECTION

C0

0

15

min. 0

disabling time to the output activation from the instru-

ment start

It establishes the time that disables the output activation from the moment of the instrument

start.
C2

0

15

min. 3

disabling time to the output activation from the previous

deactivation

It establishes the time that disables the output activation from the moment of the previous

output deactivation.
LABEL MIN. MAX. U.M. ST.

DEFROST REGULATOR

d0

0

99

(*)

8

defrost interval

It establishes the time interval that pass from the moment of the instrument start or from the

moment in which the instrument activates a defrost to the moment in which the instrument

automatically activates the following defrost.
If the parameter d0 has value 0 the instrument never automatically activates a defrost, except

what established with the parameter d4.
d3

1

99

(*)

30

defrost length

It establishes the defrost length.
d4

0

1

---

0

defrost at the instrument start

It establishes if the instrument automatically must activate a defrost at the moment of the

instrument start, as indicated:

0 =

inactive

1 =

the instrument automatically activates a defrost at the moment of the instrument start.

d5

0

99

(*)

0

delay to a defrost activation from the instrument start

If the parameter d4 has value 0 it establishes a time interval to add to the interval established

with the parameter d0; the value so obtained establishes the time interval that pass from the

moment of the instrument start to the moment in which the instrument automatically activates

the following defrost.
If the parameter d4 has value 1 it establishes the delay with which the instrument automatically

activates a defrost from the moment of the instrument start.
A manual activation of a defrost during the count of the delay established with the parameter

d5 clears the delay.
d6

0

1

---

1

locking of the displayed temperature from a defrost acti-

vation

It establishes if to lock the displayed temperature from the moment in which the instrument

activates a defrost, as indicated:

0 =

inactive

1 =

during a defrost and as long as the temperature read by the cabinet probe reaches the

working setpoint, the instrument displays the temperature read by the cabinet probe in

the moment in which the instrument activates a defrost.

db

0

1

---

0

times base for the parameters d0, d3 and d5

It establishes the unit of measure of the parameters d0, d3 and d5, as indicated:

0 =

the unit of measure of the parameter d0 is the hour and the unit of measure of the

parameters d3 and d5 is the minute

1 =

the unit of measure of the parameter d0 is the minute and the unit of measure of the

parameters d3 and d5 is the second.

ADDITIONAL INFORMATIONS
-

the symbol (*) indicates that the unit of measure depends from the parameter db.

SIGNALS AND ALARMS

SIGNALS
If the LED L1 is turned ON it means that the output K 1 is activated.

If the LED L1 flashes it means that a defrost is running.

ALARMS
If the instrument displays the indication “E2” flashing (corrupted memory data alarm) it means

that there is a corruption of the configuration data in the memory (turn OFF and turn ON again

the instrument: if to the turning ON again the alarm does not disappear the instrument must be

replaced); during this alarm the access to the working setpoint setting and the configuration

parameters setting procedures is refused and the output K 1 gets forced to the status OFF.
If the instrument displays the indication “E0” flashing (cabinet probe failure alarm) it means

that: the kind of connected cabinet probe is not proper (verify the kind of connected cabinet

probe), the cabinet probe is faulty (verify the cabinet probe integrity), there is a mistake in the

instrument-cabinet probe connection (verify the instrument-cabinet probe connection integ-

rity), the temperature read by the cabinet probe is outside the limits permitted by the cabinet

probe in use (verify that the temperature near the cabinet probe be inside the limits permitted

by the cabinet probe); during this alarm the output K 1 gets forced to the status OFF, if a defrost

is running the defrost ends and the instrument never activates a defrost.
ADDITIONAL INFORMATIONS
-

the alarm codes are related in order of precedence.

TECHNICAL DATA

TECHNICAL DATA
Case:

plastic black (PC-ABS), self-extinguishing.

Size:

74 x 32 x 65 mm (2.91 x 1.25 x 2.55 in.).

Installation:

panel mounting, panel cutout 71 x 29 mm (2.79 x 1.14 in.),

with the equipped screw or spring brackets.

Type of protection:

IP 54.

Connections:

screw terminal blocks with pitch 5 mm (0.19 in., power

supply, measure input and output) for cables up to 2.5 mm²

(0.38 in.²).

Ambient temperature:

from 0 to +60

°

C (+32 to +140

°

F, 10 ... 90 % of not con-

densing relative humidity).

Power supply:

230 Vac, 50/60 Hz.

Measure inputs:

1 for NTC probes.

Working range:

from -40 a +99

°

C.

Setting range:

from -40 a +99

°

C

Resolution:

1

°

C.

Display:

2-digit display 12.5 mm (0.49 in.) high red LED display

with automatic minus sign, output status indicator, defrost

status indicator.

Outputs:

one change-over contact 8 (3) A @ 250 Vac relay for one

½ HP @ 250 Vac compressor management.

Kind of defrost managed:

by stopping compressor, automatic and manual.

Defrost management:

for interval and length.

HOW TO ORDER

CODING SYSTEM
Instrument name:

EC 3-L20.

Desired measure input:

N (for NTC probes).

Desired power supply:

220 (230 Vac).

2