Intrepid 1640 woodburning stove, Floor protection – Vermont Casting 1640 User Manual

Page 8

Advertising
background image

8

Intrepid 1640 Woodburning Stove

30000830

Fig. 13 CSA approved Wall Pass-through.

24 ga.Sheet
Steel Support

24 ga. Sheet
Steel Support
(one side only)

Min. 18"
(460mm)

Chimney clearance to sheet steel
supports and combustibles

2" (51mm)

Min.

Chimney Flue

Chimney
Connector

Masonry Chimney
constructed to CAN/
CSA-B365

Min. 18"

(460mm)

ST276

Fig. 10 Wall Pass-through using factory-built insulated
chimney section.

Min. 9"

(230mm)

Air Space

Min. 9"

230mm

Chimney Flue

Sheet Steel
Supports

Min. 2"

(51mm)

Non-soluble
refractory cement

Solid
insulated,
listed factory-
built chimney
length set flush
with flue

Chimney
Connector

Masonry
Chimney
constructed to
NFPA 211

24 ga.Sheet
Steel
Supports

ST273

Fig. 12 Wall Pass-through with ventilated steel thimble.

24 ga. Sheet
Steel Supports

24 ga. Sheet
Steel Supports

2" (51mm) Min.

Chimney clearance to sheet steel
supports and combustibles

2" (51mm)
Min.

Chimney Flue

2" (51mm) Min.
air space

Prefab
Chimney
Section

Prefab
Chimney
Section

Chimney

Connector

Masonry Chimney
constructed to NFPA 211

ST275

Fig. 11 Wall Pass-through using single wall chimney
connector with a ventilated steel thimble.

Min. 6"
(152mm)

Chimney clearance to sheet
steel supports and combustibles

2" (51mm) Min.

Glass Fiber
Insulation

Chimney Connector

Chimney Flue

Steel Thimble
with two 1"
(25mm) Ventilated
Channels

Masonry Chimney
constructed to NFPA 211

24 ga.Sheet
Steel Supports

ST274

Canadian Requirements:

In Canada, the Canadian Standards Association has
established specific guidelines regarding wall pass-
though design. Figure 13 shows one approved method
in which all combustible material in the wall is cut away
to provide the required 18" (457mm) clearance around
the connector. The resulting space must remain empty.
A flush-mounted sheet metal cover may be used on
one side only. If covers must be used on both sides,
each cover must be mounted on noncombustible
spacers at least 1" (25mm) clear of the wall. Your local

dealer or your local building inspector can provide
details of other approved methods of passing a chim-
ney connector through a combustible wall.

In Canada, this type of installation must conform to
CAN/CSA-B365, Installation Code for Solid Fuel
Burning Appliances and Equipment.

Floor Protection

A tremendous amount of heat radiates from the
bottom plate of an Intrepid II, and the floor beneath
requires two kinds of special protection.

Heat protection is provided by a Vermont Castings
Bottom Heat Shield, part #0307.

Spark and ember protection is provided by a floor
protector, which may be any noncombustible material.

For a new hearth, we recommend a noncombustible
floor protector such as 1/4" non-asbestos mineral
board or its equivalent, or 24 gauge sheet metal. If
carpeting is present, it must be removed before
installation of the floor protector. The floor protector
may be covered with a noncombustible decorative
material if desired. When using brick, tile, or stone,
individual pieces must be mortared so sparks cannot
fall through.

When the optional 3” (75mm) short legs are used, the
bottom heat shield must be used.

Most installations will require that the bottom heat
shield be attached. Only when the stove is placed
on a completely noncombustible surface, such as
unpainted concrete over earth, may it be used
without the bottom heat shield.

Even with the bottom heat shield installed, you must
also use a floor protector.

In the United States, the floor protector required
under the stove must extend at least 16” from the front
of the stove - not from the ashlip - ( ‘E’ in Fig. 14), and
at least 6” from the sides and rear (‘D’, Fig. 14).

To meet the requirement in the United States, a floor
protector must be at least 34” wide and 40” deep.

Advertising