ISP Technologies SB 112 User Manual

Page 5

Advertising
background image

POWER DOWN THE MASTER CONTROL MODULE PRIOR TO CONNECTION TO THE HDDS SB112
MAY CAUSE POSSIBLE DAMMAGE TO THE HDDS SB112 OR THE CONTACTS PINS OF THE CAT6
CABLE DUE TO LARGE NON-SYMETRICAL INRUSH CURRENT.

Rear Panel

The rear panel POWER LED will light when power is applied from the Master Control
Module. The rear panel of the HDDS SB112 includes two RJ45 input connectors, both

for connection to a Master Control Module. A single run of Category 6 cable can be

used if the maximum length of CAT6 cable does not exceed 100 feet. Two Category 6
cables should be connected between the Master Control Module and Input A and Input

B if the HDDS SB112 is more than 100 feet away from the Master Control Module. Do
not connect another cabinet to the second RJ45 connector since this would exceed the

maximum current handling capabilities of the CAT6 cable. The maximum run length of
cable should not exceed 300 ft even with dual input CAT6 cable runs.

The HDDS SB112 will typically pull less than 2 amps of current from the output of the
Master Control Module at average listening levels. At maximum or peak level the HDDS

2210 can pull in excess of 4 amps of current. If maximum output power is desired it is
recommended to limit the length of CAT6 cable run to no more than 50 feet or use dual

cable runs. Longer runs of CAT6 cable will reduce the maximum output power of the
HDDS SB112. Connect the HDDS SB112 to any of the A, B or C outputs on the rear of

the HDDS Master Control Module as shown below. Do not connect more than two

HDDS SB112 subwoofers per zone on the Master Control Module. If long cable runs are
used requiring dual cables to connect the HDDS SB112 the zone can only power a

single HDDS SB112 subwoofer.



Advertising