Cooper Bussmann POWERPATH PS-6 User Manual

Powerpath™ nac power supplies, Notification

Advertising
background image

POWERPATH™ NAC POWER SUPPLIES

Description

The Wheelock Series PS-6 and PS-8 are 24VDC, filtered and

regulated, supervised remote power supply/battery chargers are

used for supervision and expanded power driving capability of Fire

Alarm Notification Appliance Circuits. The PS-6 provides 6 amps of

power distributed across 4 outputs, while the PS-8 provides 8 Amps

across 4 output. In addition the PS-8 provides additional room in

the chassis for accessories like an Addressable Control Module, with

mounting studs.
The Power Supplies may be connected to any 12V or 24V (FWR or

DC) Fire Alarm Control Panel (FACP) by using a Notification Appliance

Circuit (NAC) or a “Dry Contact”. Primary applications include NAC

expansion (supports ADA requirements) and auxiliary power to

support system accessories. This unit provides filtered and regulated

24VDC, up to four (4) Class “B”, two (2) Class “A”, or two (2) Class

“B” and one (1) Class “A” Notification Appliance Circuits. With the

optional plug-in PS-EXP module the unit supports (8) Class “B” or

(4) Class “A” Notification Appliance Circuits. Additionally, an auxiliary

power output of 2.5 Amps (disconnected upon AC power loss or an

alarm condition) or up to 0.240 A of constant power on the PS-8 and

0.075 A of constant power on the PS-6.
The Wheelock Power Supplies can accommodate 7 or 12 AH batteries

inside its lockable chassis. Using an external battery cabinet it can

charge up to 33 AH batteries (pending UL testing). Two FACP NAC

circuits or two “Dry” contact initiating circuits can be connected to the

inputs. These inputs can then be directed to control supervision and

power delivery to any combination of the four (4) outputs. Each output

is rated at 3.0 Amps (Class “B”) or (Class “A”) and can be programmed

to generate a steady or Code 3 Temporal Horn sound and a strobe

output under alarm condition. Total load for the PS-6 and PS-8 NAC

circuits must not exceed the power supplies rated output.
The Power Suppliesunder non-alarm condition provides independent

supervision for Class “A” and Class “B” FACP NAC circuits. In the

event of circuit trouble, the FACP will be notified via the POWERPATH

steered input (IN1 or IN2). In addition there are two sets of trouble

reporting terminals, one used for AC power loss reporting and the

other for all troubles. The AC power loss reporting, on the common

trouble terminals and on IN1 or IN2, can be delayed for either 30

seconds or 170 minutes. The AC power loss terminals will always

report the trouble within 1 second after loss of AC power.

PS-6

Approvals
• Approvals Include: UL Standard 864, 1481, California State
Fire Marshal (CSFM), Factory Mutual (FM)
• Compliant with NFPA 72

Inputs
• 120VAC, 50/60Hz, 4.25 Amps (PS-6/8) and 5.32 Amps
(PS-8) Operating Power in Alarm
• 240VAC, 60Hz, 2.42 Amps (PS-6E and 3.22 Amps (PS-8E) ‘
Operating Power in Alarm
• 24VDC Battery Backup Connection
• Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA)

FWR or DC

• Two (2) “Dry” Contact initiating Circuits
• Accepts two (2) Class “A” or two (2) Class “B” circuit inputs
• Built in battery charger for sealed lead acid or gel type

batteries


Outputs
• NAC outputs are 24VDC, 3.0 Amps each, power limited
• 8 Amps on PS-8 and 6 Amps on the PS-6 total alarm current

...Features continued on next page

U

L

®

PS-8

Notification

The PS-6 and PS-8 Power Supplies are UL Listed under UL

Standard 864, 9th Edition to be used with any 24 volt Listed

Regulated notification appliances. They include the capability

to synchronize Wheelock strobes and horns and to silence the

horn signal when horn/strobes are operating on two wires.

PS-EXP

Advertising
This manual is related to the following products: