Troubleshooting – honeywell vs8421 – Vermont Casting 360DVSL User Manual

Page 30

Advertising
background image

30

360 DVS Series Direct Vent Fireplaces

10006326

Troubleshooting – Honeywell VS8421

START

CHECK

Gas Supply On

▼

▼

▼

▼

▼

Pilot Lights With Piezo
Ignitor

•

Lockout Has Engaged. Wait 60
Seconds And Try Again.

•

For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.

•

All Wiring Connections

•

Replace Piezo Ignitor

•

Supply Line Hooked Up

•

Shutoff Valve Open

PILOT STAYS LIT

•

For Air In The Lines

•

Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.

•

All Wiring Connections

•

Replace Thermopile

•

Thermocouple Needs A Min. Of
14mv

PILOT LIGHTS MAIN
BURNER

•

Valve Is Turned On

•

Wall Switch Is Not Turned On.
Watch For Grounded Wires!

•

Thermopile Needs A Min. 325mv.

•

Plugged Burner Orifice

•

Defective Valve. Turn To Pilot,
Meter Should Read Greater Than
100mv. If Not, Replace.

SYSTEM OK

▼

YES

NO

NO

▼

NO

▼

NO

YES

YES

YES