Operating Limits

Power Output

The inverter can deliver 400 watts for about 60 minutes. The inverter must cool
for 15 minutes before it can resume operation at 400 watts. Note: The wattage
rating applies to resistive loads.

The inverter will operate most AC loads within its power rating. Some induction
motors used in freezers, pumps, and other motor-operated equipment require very
high surge currents to start. The inverter may not be able to start some of these
motors even though their rated current draw is within the inverter’s limits. The
inverter will normally start single phase induction motors rated at

1

2

HP or less.

Input Voltage

The inverter will operate from input voltage ranging from 10 volts to 15 volts.
Optimum performance will occur when the voltage is between 12 volts and
14 volts. If the voltage drops below 10.5V+/-0.3V, an audible low battery
warning will sound. The inverter will shut down if the input voltage drops
below 9.5V+/-0.3V. This protects the battery from being over-discharged.
The inverter must be turned Off then back On to reset.

The inverter will also shut down if the input voltage exceeds 15.75V+/-0.75V.
This protects the inverter against excessive input voltage. Although the inverter
has protection against over-voltage, it may still be damaged if the input voltage
was to exceed 16 volts.

Operation

Operating Limits

Troubleshooting Guide

Operation

Troubleshooting Guide

Problem/Symptom

Low output voltage

No output voltage

No output voltage after
prolonged use

No output voltage,
“Protect” indicator
lighted

No output voltage

No power to inverter

Low battery alarm
on all the time

Possible Causes

Overload

Low input voltage

Thermal shutdown

High input voltage

Short circuit

Blown fuse

Poor DC wiring

Poor battery condition

Solution

Reduce the load.

Recharge battery. Check
connections and cable.

Allow inverter to cool Off.

Reduce load, continuous operation
input current required.

Improve ventilation; Make sure ventilation
openings in the inverter are not obstructed.

Reduce ambient temperature.

Make sure the inverter is connected
to 12V battery.

Check regulation of charging system.

Check load for proper operation.

Replace fuse.

Check connections.

Make sure battery is fully charged.