Spi status words, machine 1, Spi s, Tatus – Conair MPA User Manual

Page 79: Ords, Spi c, Ppendix, Status, machine 1

Advertising
background image

UGH004/0999

C

HILLER

SPI C

OMMANDS

A

PPENDIX

B-3

Status, Machine 1

Poll: 0x21 0x42

SPI STATUS WORD

Word BIT position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

EEprom error

SET SET

*

A/D converter error

SET SET

*

CJC Error

SET SET

*

RAM hardware

SET SET

*

ROM checksum

SET SET

*

Probe Failure

*

E/M Hi temp safety

SET SET

SET

*

Prog. Hi temp safety

SET

SET SET

*

Output monitor failure

SET

SET

*

Low water pressure

SET

SET

SET

*

High deviation alarm

*

Low deviation alarm

*

Prog. Lo temp safety

SET

SET SET

*

Pump overload

SET

SET

*

Refrig. Pressure

SET

SET

*

Oil Safety

SET

SET

*

Compressor overload

SET

SET

*

Freeze Stat

SET

SET

*

Low water level

SET

SET

*

Test Mode

*

Phase error

SET

SET

SET

*

NOTES:

*

The SPI I/O list defines the Processing bit as being cleared if the unit is not processing; otherwise it is SET.

Elsewhere on the chart:

●

If a bit is not shown to be SET, it is cleared.

●

The System Alarm bit is SET if an alarm is present. It is the logical OR of Process alarm and Machine alarm.

●

Processing, System Alarm, Process Alarm and Machine Alarm bits are repeated for Process Status, Machine 1

Status and Machine 2 Status.

SPI S

TATUS

W

ORDS

Open

Alarm,

Phase

Alarm,

Lo

w current

Alarm,

High current

Alarm,

Lo

w v

olts

Alarm,

High v

olts

Reser

ved

Reser

ved

Alarm,

Lo

w pressure saf

ety limit

Alarm,

High pressure saf

ety limit

Alarm,

Lo

w temperature saf

e

ty limit

Alarm,

High temperature saf

ety limit

Alarm,

Mac

hine

Alarm,

Pr

ocess

Alarm,

System

Pr

ocessing

Advertising