THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF:

GAS WATER HEATERS

SUITABLE FOR WATER (POTABLE) HEATING AND SPACE

HEATING

1. All piping components connected to this water heater for space heating

applications must be suitable for use with potable water. In
Massachusetts, space heating piping length must not exceed 50 feet.

2. Toxic chemicals, such as those used for boiler treatment, must not be

introduced into potable water used for space heating.

3. This water heater must not be connected to an existing heating system

or component(s) previously used with a non-potable water heating
appliance.

4. When the system requires water for space heating at temperatures higher

than required for other means, such as an ASSE approved mixing valve
must be installed to temper the water for those uses in order to reduce the
scald hazard potential.


Please refer to figure 6 and figure 7 for suggested piping arrangements.