Venting (Part I) continued-

TABLE 2 -VENT CONNECTOR LENGTHS

FOR 4” (10.2 cm) DIAMETER VENT PIPE

Maximum straight

Length ft (m)

Terminating

# of 90

°

Elbows (excl.

vent term.)

48, 65 gal.

Min

straight

Length

ft (m)

Through the Wall

1 175

(53.3)

10 (3.1)

Through the Wall

2 170

(51.8)

10 (3.1)

Through the Wall

3 165

(50.3)

10 (3.1)

Through the Wall

4 160

(48.8)

10 (3.1)

Through the Wall

5 155

(47.2)

10 (3.1)

Through the Roof

0 180

(54.9)

15 (4.6)

Through the Roof

1 175

(53.3)

15 (4.6)

Through the Roof

2 170

(51.8)

15 (4.6)

Through the Roof

3 165

(50.3)

15 (4.6)

Through the Roof

4 160

(48.8)

15 (4.6)

NOTE: When using 4” (10.2 cm) vent pipe, use a 4” (10.1 cm) to 3” (7.6
cm)
reducer and exit the building wall with 3” (7.6 cm) vent pipe using the
3” (7.6 cm)
90

° vent terminal supplied. Two 45° elbows are equivalent to

one 90

° elbow.

CONNECTION TO A 3” (7.6 CM) TO

4” (10.2 CM) REDUCER

CONNECTION TO 3” (7.6 CM)

VENT PIPE

Figure 2

IMPORTANT

All of the Venting connections must be leak checked with a soap and
water solution upon initial start up of the water heater. Any leaks must
be repaired before continuing operation of the water heater.