LAARS Stor - Installation, Operation and Maintenance Instructions User Manual

Page 31

Advertising
background image

31

Maintenance continued-

a. Turn the water heater electricity off for the zone containing the

indirect-fired heater. Flow water until the discharge is cool or
allow enough time for the potable water to cool naturally.
Connect a hose to the drain valve. Locate the hose’s discharge
in an area where any remaining hot water will not cause any
damage or injury.

b. Open the drain valve to flush any sediment out of the bottom to

the heater.

c. Shut off the cold water supply. Make sure all hot water fixtures

and circulating pumps are turned off.

d. Wait for water flow from the hose to stop. Remove the anode

using a socket of the appropriate size. Do not use an impact
wrench.

e. Inspect and replace the anode as required. Use pipe tape or

sealant when reinstalling the anode.

f. Close the drain valve. Open a hot water fixture to allow air to

escape. Open the cold water supply to the heater and allow the
tank to fill.

g. Check your anode and drain valve for leaks.
h. Turn the water heater electricity on for the zone containing the

indirect-fired heater.

4. Sediment (Annual, but harsh water quality may dictate more

frequent service) – Depending on water conditions, a varying
amount of sediment may collect in the tank. Levels requiring
service are indicated by a small temperature difference in the supply
and return lines (See also “Scale” below). Repeated flushing
usually clears such material. As a preventive measure, water should
be drawn from the tank at the drain valve until it runs clear.

5. Scale (Annual) – Hard water may cause scale to build-up on the

outside of the heat exchanger coil. A water softener will prevent
this problem (See also “Sediment” above). Symptoms would be
reduced recovery capacity or reduced temperature differential
between boiler supply and return lines. Repeated flushing should
resolve the problem.

Advertising
This manual is related to the following products: