Bacnet mstp communication menu, Bacnet mode, Bacnet baud rate – LAARS M4-LHS - Installation Manual User Manual

Page 26: Ms/tp address, Bacnet id

Advertising
background image

HT# 059295-00

A

26

M4-LHS installation and Operation Manual

BaCNET MSTP COMMuNiCaTiON MENu

-------- SETTINGS ----

Season

Winter

System Target 140

o

F

<System Settings>

<Maintenance>

<System Startup>

BACK ▲ ▼ SELECT

-- ARE YOU SURE? --

No

Yes

BACK ▲ ▼ SAVE

--- BACNET MODE ---

Disable

Enable

BACK ▲ ▼ SAVE

- BACNET BAUDRATE -

9600

19200

38400

BACK ▲ ▼ SAVE

----MS/TP ADDRESS----

64

[ ]

BACK ▲ ▼ SAVE

---- BACNET ID ----

477000

[

]

BACK ▲ ▼ SAVE

When using the M4-LHS in a BACnet MS/TP network, the use of BACnet Interface Module is

required. In addition, each of the Boiler Type and Sensor Type Startup menu option will offer

a different list of BACnet variables. See "Boiler Type" on page 19. See "Sensor Type" on page

19. Also, see "Hybrid - Outdoor Reset - BACnet Variable list" on page 44

BaCnet Mode

Enable, Disable

Default: Disable

Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode

• This menu option enables or disables the BACnet MSTP capability. When enabled,

additional BACnet settings shall be available for further customizing.

• Note that if this option was enabled while no BACnet communication is present, the BAcnet

error message will supersede other messages. See "Display Messages" on page 38.

--- BACNET MODE ---

Disable

Enable

BACK ▲ ▼ SAVE

BaCnet Baud rate

9600, 19200, 38400

Default: 19200

Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode/BACnet Baudrate

• For the control to communicate over a BAcnet MS/TP network, it must use the same Baud

rate as the rest of the network. The control offers three Baud Rates.

• If communication was not successful, the baud rate could be the cause. Check with the

network administrator for the network baud rate. Then match it on the control.

- BACNET BAUDRATE -

9600

19200

38400

BACK ▲ ▼ SAVE

MS/TP address

1 to 127

Default: 64

Button: MENU/<System Startup>/.... /BACnet Mode/BACnet Baudrate/ MSTP Address

• Each device on the MS/TP network must have a unique address.

• This is the MS/TP address on a RS485 network. Its MS/TP range is 1 though 127.

• The MS/TP address must be provided by the Network Administrator.

----MS/TP ADDRESS----

64

[ ]

BACK ▲ ▼ SAVE

BaCnet iD

1 to 4,000,000

Default: 477,000

Button: MENU/<System Startup>/.... / MSTP Address / BACnet ID

• The BACnet ID is a unique 32 bit number that identifies the control within the BACnet

network. No two ID shall be the same even if dealing across networks.

• It must be provided by the BACnet Network Administrator.

---- BACNET ID ----

477000

[

]

BACK ▲ ▼ SAVE