High and low fire adjustments on the gas valve, Magnatherm boilers and water heaters – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 65

Advertising
background image

MagnaTherm Boilers and Water Heaters

Page 61

Model

Gas Type

High Fire CO

2

Low Fire CO

2

Pressure Differential

2,000

Natural

9.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc*

Propane

10.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc*

2,500

Natural

9.0% ± 0.2

0.25% lower than high fire CO

2

0.9” to .09” wc

Propane

10.0% ± 0.2

0.25% lower than high fire CO

2

0.9” to .09” wc

3,000

Natural

9.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc

Propane

10.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc

3,500

Natural

9.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc*

Propane

10.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc*

4,000

Natural

9.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc*

Propane

10.0% ± 0.2

0.25% lower than high fire CO

2

0.5” to 1.2” wc*

* - Only check the pressures if there are problems getting the CO

2

and CO values in range.

High fire adjustment

Gas Valve

Low fire adjustment

Figure 31. High and Low Fire Adjustments on the Gas Valve

Table 16. CO

2

Range and Pressure Differential