4 combustion and ventilation air supply, Laars heating systems – LAARS Mighty Therm VW-PW (Sizes 175-400) - Installation, Operation and Maintenance Instructions User Manual

Page 6

Advertising
background image

LAARS Heating Systems

Page 6

Figure 11. Standard base for combustible floor.

Figure 13. Typical roof mounting with standard

combustible mount base.

Figure 12. Typical roof mounting.

Figure 10. Outdoor location installation.

Figure 9. Incorrect outdoor installation.

Concrete slab must extend out a
minimum of 12 in. (305mm) on
all sides.

LAARS

UNIT

(Side View)

Base For Combustible Floors

Roof - Wood and Steel Construction

Mounting Platform must extend
out a minimum of 12 in.
(305mm) on all sides.

LAARS

UNIT

(Side View)

Base For Combustible Floors

Raised Mounting

Platform (Wood)

20 Gauge
Galvanized
Sheet Metal
Cap

Roofing

Base Rail

Flashing

Roof

LAARS

UNIT

(Side View)

Base For Combustible Floors

Flashing

4x4 Stringer

Roof

Base Rail

20 Gauge
Galvanized
Sheet Metal
Cap

Roofing

Avoid locations where wind deflection off nearby

structures might cause wind loading and downdraft
conditions. Where downdraft conditions exist, locate
the heater at least 3 feet (0.91 m) from the structure.

2.3.3 Flooring - Typical Installation
Do not
install the heater directly on carpeting

without placing a non-combustible platform between
the carpeting and the heater. If the heater is installed in
a carpeted alcove, the entire floor of the alcove must
be covered by a non-combustible panel. The panel
must be strong enough to carry the total weight of the
heater and all piping, pumps, and any other equipment
attached to the heater. For rooftop installation, see
Figure 11 through Figure 13.

2.4 Combustion and Ventilation

Air Supply

All indoor installations must have openings to

outside air for combustion, ventilation and dilution of

Advertising