2 initial start-up – LAARS Mighty Therm AP (Sizes 500-1825) - Installation, Operation and Maintenance Instructions User Manual

Page 11

Advertising
background image

Mighty Therm Commercial Pool Heating Boiler

Page 11

Figure 11 - Control Locations

Rating Plate

Manual
Pilot
Valve

Water
Circulating
Pump

Safety
Gas
Valve

Operating/Safety
Gas Valve

Ignition Control

Flow
Switch

Pressure
Relief
Valve

Power
(On/Off/Auto)
Switch

Pump Time
Delay Relay

Operating
Controls

Terminal Strip

In

Out

Hi-Limit

Manual
Main
Gas Valve

Figure 12 - Safety Components

Manual Reset

High Limit

Flow

Switch

Low Water

Cutoff

(Optional)

Figure 13 - Pilot Burners

Thermo-

couple

Spark Ignition

Standing Pilot

5. Flow

Switch:

Standard on all AP pool heating heaters. The switch
is mounted in a tee fi tting on the outlet header.
This is a paddle type switch which is defl ected
by the water fl ow in the fi tting. Any condition
which interrupts or decreases the fl ow through the
secondary loop will shut down the burners.

6.

Low Water Cut Off (optional):

The low water cut off automatically shuts off heater
whenever water level in the heat exchanger drops
below probe level. It is located in the inlet header,
and is a manually reset device.

3.2 Initial Start-Up

WARNING

Do not use this appliance if any part has
been under water. Immediately call a qualifi ed
service technician to inspect the heater. The
possible damage to a fl ooded appliance can
be extensive and present numerous safety
hazards. Any appliance that has been under
water must be replaced.

Newly constructed pools may have low pH, and higher
levels of calcium hardness or construction debris. Do
not allow pool water to circulate through the pool heater
until the water has been fi ltered to remove all debris,

Advertising