NeoTherm’s efficiency is higher with lower return

water temperatures. Therefore, to get the most of low return

temperature with multiple boilers, pipe as shown in Figures 17-19.
NeoTherm NTV models 150-500 can be ordered with or

without a pump included.
NeoTherm NTH models 80-500 can also be ordered with or

without a pump included.
NeoTherm with a pump MUST be piped in a primary-

secondary fashion (using either piping or a hydraulic

separator) such that the pump that is mounted on the boiler

ONLY serves the boiler.
When the pump is supplied by Laars, the NeoTherm boiler

must be located within 15 feet (4.6m) of the supply and return

header (or the hydraulic separator). Pumps supplied by Laars

are sized for a maximum of 30 feet (9.1m) of connection size

piping and the headloss of the boiler only. (See Table 7.)
If longer pipe lengths are required, the pump should be sized

for the boiler per Table 7 and for the piping it will serve,

and should be supplied to job separately. Even with pumps

supplied by others, Laars strongly recommends primary-

secondary piping.

6A.2 NTH Cold Water Make-Up

1.

Connect the cold water supply to the inlet connection of

an automatic fill valve.

2.

Install a suitable back flow preventer between the

automatic fill valve and the cold water supply.

3.

Install shut off valves where required.

The boiler piping system of a hot water heating boiler

connected to heating coils located in air handling appliances

where they may be exposed to refrigerated air circulation

must be equipped with flow control valves or other automatic

means to prevent gravity circulation of the boiler water during

the cooling cycle.
A boiler installed above radiation level, or as required by the

authority having jurisdiction, must be provided with a low

water cutoff device either as a part of the boiler or at the time

of boiler installation.

NTH

PIPE SIZE,

NTV

PIPE SIZE,

SIzE

INCHES

SIzE INCHES

80

1

– n/a

105

1

n/a

150

1

150

210

199

285

285

2

399

399

2

500

500

2

600

600

2

750

2

750

2

850

2

850

2

Table 9 - Water Connection Pipe Sizes

Section 6A -

WATER CONNECTIONS -

NTH BOILER

Section 6 is divided into two parts. Section

6A covers NTH units designed for hydronic

heating. Section 6B covers NTV models, which

are designed exclusively for “volume water”

domestic hot water applications. Refer to the

proper section for instructions on installing

and piping your product. Refer to Table 9 for

the connection pipe sizes required.

6A.1 NTH System Piping -

Hot Supply Connections

NOTE: This appliance must be installed in a closed

pressure system with a minimum of 12 psi (82.7kPa)

static pressure at the boiler.
Hot water piping should be supported by suitable hangers or

floor stands. Do not support piping with this appliance. Due

to expansion and contraction of copper pipe, consideration

should be given to the type of hangers used. Rigid hangers

may transmit noise through the system resulting from the

piping sliding in the hangers. It is recommended that padding

be used when rigid hangers are installed. Maintain 1” (2.5cm)

clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to a drain or

in a manner to prevent injury in the event of pressure relief.

Install an air purger, an air vent, a diaphragm-type expansion

tank, and a hydronic flow check in the system supply loop.

Minimum fill pressure must be 12psig (82.7kPa). Install

shutoff valves where required by code.