Understanding operation concept, Warning, Reset ratio curves – LAARS S8Ext - Installation Manual User Manual

Page 5: Page 5 laars sequencing controls s8 & s8ext, Reset ratio/outdoor reset, F outdoor temp. and 100, F, this means the temperature has fallen 20

Advertising
background image

Page 5

LAARS Sequencing Controls S8 & S8EXT

UNDERSTANDING OPERATION CONCEPT

The S8 has multiple operating modes that satisfy most hydronic systems. In heating, it can

change the System Set Point based on outdoor temperature. Or, it can sequence stages to

achieve an adjustable fixed Set Point in either heating or cooling.

In Outdoor Reset, the S8 controls a hot water heating system to provide a building with

comfortable and even heat levels. The S8 varies the temperature of the circulating heating

water in response to changes in the outdoor temperature. The heating water temperature is

controlled through the sequencing of the stages.

The S8 also controls the system circulating pump with an adjustable Outdoor Cutoff. In heating,

when the outdoor temperature is above Outdoor Cutoff, the pump is off and no heating water is

circulated through the system. When the outdoor temperature drops below the Outdoor Cutoff,

the system pump relay is activated and the heating water circulates through the system. The

temperature of the heating water is controlled by the Reset Ratio, Water Offset, and changes

with Outdoor temperature. In cooling applications, the outdoor cutoff turns off the cooling

units and system pump when the outdoor temperature rises above the outdoor cutoff setting.

RESET RATIO/OUTDOOR RESET

When a building is being heated, heat escapes through the walls, doors, and windows to

the colder outside air. The colder the outside temperature, the more heat escapes. If you

can input heat into the building at the same rate that it is lost out of the building, then the

building temperatures will remain constant. The Reset Ratio is an adjustment that lets

you achieve this equilibrium between heat input and heat loss.

The starting point for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor Temperature

: Heating Water Temperature) ratio. This means that for every degree the outdoor

temperature drops, the temperature of the heating water will increase one degree. The

starting point of the curves is adjustable, but comes factory selected at 70

°

F Outdoor

Temp. and 100

°

F Water Temp. For example with a 1.00 (OD):1.00 (SYS) ratio, if the

outdoor temperature is 50

°

F, this means the temperature has fallen 20

°

from the starting

point of 70

°

F. Therefore, the heating water temperature will increase 20

°

to 120

°

F.

Each building has different heat loss characteristics. A very well insulated building will

not lose much heat to the outside air, and may need a Reset Ratio of 2.00 (OD):1.00

(SYS) (Outdoor:Water). This means the outdoor temperature would have to drop 2

degrees to increase the water temperature 1 degree. On the other hand, a poorly insulated

building with insufficient radiation may need a Reset Ratio of 1.00 (OD):2.00 (SYS).

This means that for each degree the outdoor temperature dropped the water temperature

will increase 2 degrees. The S8 has a full range of Reset Ratios to match any buildings

heat loss characteristics.

A heating curve that relies not only on Outdoor temperature but also on type of radiation

will improve heat comfort. The following are suggested initial settings for different types

of radiation based on average building insulation and heat loss. The contractor can fine

tune these adjustments based on the specific building need.

Type of Radiation in Building

Reset Ratio

Offset

Radiators (Steel & Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Baseboard (Finned copper tube& Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Radiant (High Mass/Concrete)

4.00 (OD) : 1.00 (SYS)

-10˚F

Radiant (Low Mass/Joists)

2.00 (OD) : 1.00 (SYS)

-10˚F

Fan Coils & Air Handlers

1.00 (OD) : 1.00 (SYS)

20˚F

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

110

100

90

80

Outdoor Temperature

W

at

er

Te

m

pe

ra

tu

re

70

40

50

60

150

140

130

120

1:4

With a 0° Offset, the
ratio curves begin at
100° Water Temperature.

With a -20° Offset, the
ratio curves begin at
80° Water Temperature.

With a +20° Offset, the
ratio curves begin at
120° Water Temperature.

1:4

1:4

1:1

1:1

1:1

4:1

4:1

4:1

90

100

+20 Offset

-20 Offset

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

1:4

1:1

4:1

Colder

Warmer

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

100

120

110

130

140

150

160

180

170

190

200

210

220

1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1
4:1

W

ater

Temperature (in °F)

Reset Ratio Curves

Reset Ratio is Presented as

Outdoor Temp. : Water Temp. Ratio

1:4

8:1

WARNING

When controlling a non condensing

boiler, minimum boiler water

temperature must be set to boiler

manufacturer specifications. In that

case, system temperature must not

go below such temperature.

Advertising
This manual is related to the following products: