Troubleshooting, No led lights, No communication – LAARS X-BAC BACnet Interface Module - Install and Operating Manual User Manual

Page 6: Specification

Advertising
background image

6

X-BAC BACnet Interface Module Installation and Configuration Manual

HT#

059294-00

B

TrOuBLeSHOOTIng

nO LeD LIgHTS

• The RJ45 connection to the control powers the BACnet Interface Module. If all LEDs are off, then check the cable connecting the

module to the control. The cable consist of 8 wires. Check each of the color-coded wires continuity in the cable using a continuity

meter.

nO COMMunICATIOn

• Check the Yellow and Green LEDs. If the Yellow LED is continuously On or Off, then check the cable connecting the module to

the control.

• If the Green LED is continuously On or Off, then check the cable connecting the module to the BACnet network.

• Make sure that the control's Baud Rate and the BACnet Network's are the same. See "BACnet Baud Rate" on page 5.

SPeCIfICATIOn

Control Communication . . . . . . . . . . . . . . . . . . . . . . . . . . RJ45 to control (Cable is provided)

BACnet MS/TP Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-wire

Extension Communication. . . . . . . . . . . RS485 (RJ11) to Extension (Cable packaged with Extension)

LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Red, Yellow, and Green

Dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-¾” x 3-⅝” x 1”

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Pound

Advertising