LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 36

Advertising
background image

Page 36

LAARS Heating Systems Company

Gas valve regulation problems can also cause

delayed ignitions. See “Gas valve calibration”.

Incorrect gas orifice – Check orifice size.

A defective burner can cause a delayed ignition

during operation or at shutdown. If the gas supply

pressure is proper the gas valve is functioning properly

and the gas orifice is correct, the burner should be

inspected. To inspect it, remove the blower. The burner

is retained by the blower and it will drop out of the

bottom of the chamber when the blower is removed.

There should be no distortion or perforations in

the burner other than the punched holes. Replace if

indicated.

11.2 Short Cycling

Possible causes

a. Reduced system flow - EDP

b. Thermostatic union (EDP) or anti-condensing

valve not opening (EBP).

c. T-T wires cross connected (jumped) – improper

installation - EBP or EDP/EDN

d. Leakage of flue products into the combustion

air stream – Direct Vent Installations only, see

Section 9.2.3, Resolving Lockouts.

11.3 Noisy Operation

There are two principal sources of noisy

operation:

a. Combustion - high pitched noise - whistle or

hoot.

b. Boiling (kettling) - lower frequency noise which

varies with temperature - moan.

Many times it is difficult to determine the source

of the noise or if it is combustion related or boiling

related. Combustion noises always have the same

frequency; however, their volume may change from

the time that the burner first fires to the time that

it shuts off. A boiling noise is identified by rapidly

raising or lowering the system water pressure while

the noise is present. A change in the pitch or intensity

of the noise indicates a boiling problem.

Combustion noise occurs at any boiler discharge

temperature and is heard the loudest at the flue outlet

(especially on units that are sidewall vented). There

are two basic causes for the noise, rich mixture (high

CO

2

or low O

2

) or cross contamination. The mixture

is determined by measuring the percent O

2

or CO

2

in

the flue products. O

2

readings lower than 4½ % or CO

2

readings higher than 9¼ % (natural gas) and 10.8%

(LP) will often cause combustion related noise. The

rich mixture could be caused by the mis-calibration of

the gas valve (offset adjustment) or by the gas orifice

size. To eliminate the noise; first, check the gas valve

calibration. If it is correct, install a smaller gas orifice

so that the O

2

will rise above 4½% or the CO

2

will

drop to 8½% (natural) or 9½% (LP).

The CO

2

& O

2

readings may be influenced by

cross contamination. Suspect cross contamination if

the noise returns when the front panel is replaced.

Boiling (kettling) may occur at boiler discharge

temperatures from 170°F to 210°F. The temperature

at which it starts will vary from one installation to

another. The primary cause of the problem is poor heat

transfer on the inside of the boiler coil. This may be

caused by foaming due to excessive concentration of

antifreeze in the system or by scaling from the boiler

water due to hardness of make up water.

Plumbing antifreezes should never be used in a

boiler system. Only boiler antifreezes, with effective

antifoamants, are appropriate for the ENDURANCE

boilers.

NOTE: The concentration of appropriate antifreeze

should be always be kept as low as possible to

minimize its effect on heat transfer and efficiency.

The method for eliminating the boiling noise

is the same regardless of the cause. However, if

antifreeze in the system is suspected of being the

cause, the concentration (<35%) and type should be

investigated.

Moisture

Although it is not a primary cause of lockouts,

moisture in the combustion chamber may cause

lockouts by weakening the flame signal to the boiler

control. It should be suspected if the boiler temperature

does not rise above 160°F during long periods of

operation. This condition can be caused by a defective

thermostat in the thermostatic union of EDN or EDP

boilers (or the omission of the thermostatic union at

installation) or failure of the anticondensing valve in

the EBP (combi) boilers. Moisture can also get into the

combustion chamber through an incorrectly pitched or

incorrectly installed flue pipe (pitched back toward the

boiler without a condensate trap). The flue assembly

of EBP, EDN and EDP boilers installed as Direct Vent

boilers should always pitch down from the boiler.

11.4 Insufficient Hot Water (EBP only)

Possible cause:

a. No flow restrictor (supplied with unit - field

installed)

b. Water flow switch failure
c. Mixing valve setting or failure
d. Domestic hot water (DHW) heat exchanger

contamination

The most common cause for insufficient hot

water complaints results from failure to install a flow

restrictor. The absence of a flow restrictor allows

water to pass through the heat exchanger at a greater

rate than the boiler output is capable of heating to the

desired temperature.

Advertising