Mighty Max Volume Water Heater

Page 5

Figure 3. Heater Gas Valve Arrangement.

Notes: 1. These numbers are based on 1/2 inch (13mm) water column pressure drop.

2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing.

Table 3. Natural Gas and Propane, Pipe Size Requirements.

SIZES:

320M, 400M

Venturi

Air Shutter

Enclosure

Automatic,

Regulator

and

Redundant

Gas Valve

Mixture

Plenum

Filter

Housing

Blower

Motor

NOTE: The above diagram is a representation, actual venturi
assembly may vary depending upon heater size.

2.6 Gas Supply and Piping

Review the following instructions before

continuing the installation.
1.

Gas piping installation must be in accordance

with the latest edition of ANSI Z223.1/NFPA 54.

In Canada, the installation must be in accordance

with CSA B149.1 and all local codes that apply

(see Figure 3 for heater gas valve arrangement).

2.

Check the rating plate to make sure the heater is

fitted for the type of gas being used. Laars

heaters are normally equipped to operate below a

2000 foot (610m) altitude. Heaters equipped to

operate at high altitudes have appropriate

stickers or tags attached.

3.

The figures in Table 3 should be used to size the

gas piping from the gas meter to the heater.

Check local codes for BTU/h capacity required.

4.

Install a sediment trap (drip leg) ahead of the gas

controls (see Figure 4). Fit the trap with a

threaded cap which can be removed for cleaning.

5.

When required by code, install a second manual

gas shutoff valve. Do not remove manual shutoff

valve supplied with the heater.

6.

Disconnect the heater and its individual shutoff

valve from the gas supply piping system during

pressure testing of the system at pressures higher

than 1/2 psi (3.5 kPa). Isolate the heater from the

gas supply piping system by closing its

individual manual gas shutoff valve during any

pressure testing of the gas supply piping system

at test pressures equal to or less than 1/2 psi

(3.5 kPa).

7.

Gas supply pressures to the heater are listed in

Table 4.

Supply Pressure

Natural Gas

Propane Gas

Water Column

in.

mm

in.

mm

Minimum

5

127

9

229

Maximum

9

229

14

356

Table 4. Gas Supply Pressure Requirements.

the top of the heater or the back, and combustion air

can be obtained from the room where the heater is

installed or ducted directly to the heater from outdoors

(see Sections 2.8 through 2.11 for details).

Distance from Gas Meter or Last Stage Regulator

0-100 feet

100-200 feet

200-300 feet

0-30m

30-60m

60-90m

Natural

Propane

Natural

Propane

Natural

Propane

Size

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

320M

1.25

32

1.25

32

1.50

38

1.25

32

1.50

38

1.50

38

400M

1.25

32

1.25

32

1.50

38

1.25

32

2.00

51

1.50

38