Mighty Therm LO-NOx Hydronic Boiler

Page 7

2.3 Site Location

2.3.1 Installation Information

WARNING

Improper installation or maintenance can cause
nausea or asphyxiation from carbon monoxide in
flue gases which could result in property damage,
severe injury, or death.

MISE EN GARDE

Une mauvaise installation ou un entretien inadéquat
peut provoquer la nausée ou l’asphyxie en raison
de la présence de niveaux dangereux de monoxyde
de carbone dans les résidus de combustion et peut
entraîner des dommages matériels, des blessures
ou même la mort.

Avoid placing the boiler in locations where it can

cause damage by water or condensate leakage. If this is
not possible, provide a suitable drain pan under the
boiler to catch and divert any leakage. The pan must
not restrict air flow around the boiler.

Locate the boiler to provide adequate clearance

on all sides for inspection, service and to provide
adequate air circulation for proper operation.

Locate the boiler so the clearances from

combustible surfaces shown in Table 1 and Figure 17
are met.

Locate the boiler on a waterproof floor with a

floor drain and a 6 inch (15.2 cm) minimum curb on all
four sides to protect the building if boiler repairs are
needed.

inches clearance between the automatic vent
damper and combustible construction, and be
sure to allow access for servicing the damper.

WARNING

Do not force the damper to open or close by moving
the damper blade, turning the shaft, or turning the
position indicator. Doing so can cause an unsafe
condition, leading to property damage, injury or
death.

MISE EN GARDE

Ne pas forcer l’ouverture ou la fermeture du registre
en faisant bouger le volet du registre, en tournant la
tige ou en tournant l’indicateur de pression. Cela
peut engendrer une situation non sécuritaire
susceptible de provoquer des dégâts matériels, des
blessures ou la mort.

Figure 16. Vent Damper Installation (Model 250 only).

Indoors

Outdoors

Clearance from:

inch

cm

inch

cm

Top

37

94

Unobstructed

Water conn. side

12

30.5

Unobstructed

Opposite side

6

15.2

6

15.2

Front

Alcove

Unobstructed

Rear

6

15.2

6

15.2

Vent*

6

15.2

Flooring: Combustible
Service clearance = 36 inches (91.4cm) at front of boiler,
and 18 inches (46cm) at water connection side.
*1" (2.5cm) if double wall vent is used.
6" base for outdoor boiler is required.

Table 1. Minimum Boiler Clearances

from Combustible Surfaces.

OUT OF

PRODUCTION