24 volts across 1&4

(blue&yellow) and 2&4

(orange&yellow ) on

damper end of

harness?

N

Y

Main

burners

light?

24 volts across

red damper lead

and yellow

transformer

lead?

* Refer to standing pilot
or intermittent ignition
troubleshooting chart
(page 39 or 40).

* Defective damper
* Defective or loose
damper harness
* Obstruction in
path of damper
blade

24 volts across

standing pilot gas

valve terminals or

terminals 5&6 on

S8600 module?

24 volts

across spill

switch?

*Chimney blockage
*Chimney system not
contructed in accordance
with Parts 7 and 10 of
National Fuel Gas Code .
*Down draft
*Inadequate combustion air
supply in boiler room

Y

N

Y

24 volts

across rollout

switch?

*Loose electrical
connection in spill
switch or rollout
switch wiring or gas
valve common

*Rollout switch open.
Replace with exact
replacement (see parts
list). Check for blocked
heat exchanger.

Y

N

N

Y

N

Do burners shut

down when water
level drops below

cut-off point?

END

*Grounded probe or probe
lead
* Defective L.W.C.O.
DO NOT OPERATE BOILER
UNTIL THIS PROBLEM IS
CORRECTED

Do burners

shut down when

pressure

exceeds limit

setting?

* Defective
pressure limit
control
* Blockage in
siphon tube

Y

Y

N

N

* Defective or
loose damper
harness

* Defective or loose
damper harness
* Defective damper
motor
*Obstruction in path
of damper blade

N

Y