6. Program

Function

Display

Possible actions

Comments

Access

Exit

Push Pro for 3 seconds

Push Pro for 3 seconds

Master must be off

1. Nozzle


nozzle

setup

↓ to select another step

Pro to enter nozzle setup (1.1)


Push Pro for 3 seconds to escape
program

1.1

Iso 04

0.40 g/m

Iso 04

1.31 l/m

↑ ↓ to select a nozzle

Pro to validate selected nozzle


If a programmable nozzle is needed
select programmable nozzle and
push Pro go to step 1.2:
programmable nozzle value.

1.2

@ 40 psi

1.43 g/m

@ 2 bar

1.12 l/m

↑ ↓ to modify gal/min value

Pro to validate value

US Units
Enter nozzle rating in gallons
/ minute @ 40PSI

Metric Units
Enter nozzle rating in liters /
minute @ 2Bar

2. Pressure
sensor

pressure

setup

↓ to select another step

Pro to enter calibration (2.1)


Push Pro for 3 seconds to escape
program

Maximum pressure allowed
by the sensor.

2.1

Max prs

150 psi

Max prs

10 bar

↓ to modify max pressure value

Pro to validate max pressure and go

to the zero PSI calibration (2.2)

Max pressure rating for the
sensor can be found on the
sensor or by contacting your
70 series monitor distributor.

2.2

Calibr.

At 0 psi

Calibr.

At 0 bar

Pro for auto calibration of the

pressure sensor at zero PSI

!!! Be sure there is no
pressure in the
system !!!

2.3

Delta pr

5

↓ to modify value

Pro to validate value


This value is used to compensate
the pressure drop between pressure
measurement point and nozzle.
If not needed, set it to 0.The higher
the value, the higher the
compensation

.