Specifications of the main rack components – Toa FS-970 SERIES User Manual

Page 49

Advertising
background image

24 VDC

0.6 A

Composite audio signal tone (1st signal, 2nd signal, Warning Announcement,
Evacuation Announcement, False Alarm Announcement)

1st basement - 22nd floor, 1st basement - 5th floor, stairs, elevator, roof top,
penthouse, gymnasium, auditorium, and no floor.
Notes
• Expandable to up to 330 zones (floors) by expanding the flash memory card

(option).

• Additional expense is charged for writing into the flash memory card.

English

Interlock or all-zone interlock

Two-floor interlock or two-floor non-interlock

Warning Announcement Interlock or Warning Announcement Non-interlock

30 seconds - 15 minutes 30 seconds (set in 30-second units with the internal
DIP switches)

Off/0 - 15 minutes 30 seconds (set in 30-second units with the internal DIP
switches)

PA microphone (attachment) : –40 dBV, 600

Ω, unbalanced, 4-pin jack

General pre-amplifier :

0 dBV, 600

Ω, balanced, phone jack

Timer (time signal) :

0 dBV, 600

Ω, unbalanced, phone jack

Attenuator-free audio input :

0 dBV, 600

Ω, unbalanced, phone jack

Emergency/general output : 0 dBV, 15

Ω, balanced, phone jack

10 individual zones + all zones, 5 groups (expandable to up to 330 individual
zones by expanding the EP-029)

Status:

Voice alarm on, microphone announcement on,
Warning Announcement on, Evacuation Announcement on,
False Alarm Announcement on, abnormality in progress,
General Broadcast on, system check in progress

Output format: Open collector output, withstand voltage: 24 VDC,

current capacity: 0.1 A

Voice operation guide and screen display (30 characters x 4 lines)

3 W

Panel: ABS resin, black
Case: Zinc-plated steel plate (1 mm thick)

482 (w) x 221.4 (h) x 135.5 (d) mm

4.5 kg

Chime switch assembly x 1, balanced phone plug x 1, fuse (2 A) x 1,
balanced dual-plug cord x 1, PA microphone (uni-directional, dynamic type) x 1,
rack mounting screw x 4, name label (for individual zones) x 2,
name label (for zone group) x 1

49

15. SPECIFICATIONS OF THE MAIN RACK COMPONENTS

• Integrated Control Panel EP-0510

Power Source

Current Consumption

Emergency Alarm

Fire Floor Information

Fire Floor Information
Language

Fire Alarm Interlock
Mode

Two-floor Interlock
Mode

Warning Announcement
Interlock

Evacuation
Announcement Interval

All-zone Broadcast
Interval

Input

Output

Output Control

Broadcast Status
Output

Function

Monitor Speaker

Finish

Dimensions

Weight

Accessories