Toa SX-2000 Series Manual User Manual
Page 120

Zone monitor indicator
Selection indicator
Green
Yellow
4
All-Zone Call key
10-15
Chapter 10: OPERATION
Step 3. When making broadcast using the RM-200SF,
follow the procedures below.
• Press the All-Zone Call key (4) to select all zones.
In this event, the Selection indicator lights.
• Press the Talk switch (5), then make voice
announcements to all zones.
In this event, the Broadcast status indicator lights
yellow, and the Microphone indicator lights green.
Also, the Zone monitor indicator of the All-Zone
Call key (4) lights yellow.
Zone monitor indicator
Selection indicator
Green
4
All-Zone Call key
5
Talk key
Green
Yellow
Broadcast Status Indicator
Microphone Indicator
Tip
When a Fireman's Microphone announcement interrupts a message broadcast, the broadcast mode
that follows Fireman's Microphone announcement completion can be set to either "Continue" for
continuous EV message broadcast or "Silent" for broadcast termination. This setting can be made by
using the SX-2000 Setting Software.
Step 4. Terminate the Emergency status.
Press the Emergency Reset key (3).
The reset message is broadcast to the entire zone, and the
Reset indicator of the Emergency Reset key (3) lights while the
message is broadcast.
After the message broadcast completion, the SX-2000 system is
restored from Emergency status to the General-purpose
broadcast status, and the Emergency status indicator (1) built in
the Emergency key goes off.
Reset indicator
Green
3
Emergency Reset key
1
Emergency key
Goes off