FIGurE 17: InDIrEct WatEr HEatEr FIElD WIrInG

Feeder Wiring for Boilers Equipped with Hydrolevel cG450 low Water cut-offs

1) Using Hydrolevel VXT-120 feeder - Do not alter factory boiler wiring. Connect VXT-120 to CG450 as follows:

Connect the BlacK lead on the feeder to terminal a on the CG450.

Connect the WHItE lead on the feeder to terminal 2 on the CG450.

2) Using McDonnell & Miller WF2-U-120 feeder - Do not alter factory boiler wiring. Connect WF2-U-120 to CG450A as

follows:

Connect terminal 1 on the feeder to terminal a on the CG450.

Connect terminal 2 on the feeder to terminal 2 on the CG450.

Connect terminal 3 on the feeder to terminal 1 on the CG450.

Feeder Wiring for Boilers Equipped with McDonnell & Miller low Water cut-offs

Figures 18a and 18b show feeder wiring for McDonnell & Miller #101A, McDonnell & Miller WF2-U-120 and Hydrolevel

VXT-120 feeders on boilers equipped with #67 low water cut-offs.