Outdoor reset control – TriangleTube 399 Solo User Manual

Page 59

Advertising
background image

53

Outdoor Reset Control

Graph 1 illustrates Parameter 4 adjusted to 140ºF target temperature at 0ºF outdoor
air temperature

Table 3: Outdoor Air Temperature Reset (Example)

90

20

60

100

140

180

70

64

50

30

10

0 -10

86

Bo

ile

r T

em

pe

ra

tu

re

(

F)

Outdoor Air Temperature ( F)

Parameter 4 Set Point

Parameter 10

Set Point

Pa

ra

m

et

er

1

2

Se

tti

ng

Pa

ra

m

et

er

1

1

Se

tti

ng

Graph 1: Outdoor Air Temperature Reset Curve (Example)

Note: Factory setting of Parameter 4 is 186ºF.

Outdoor

Temperature

Boiler target Temp.

Based on Outdoor Temp.

0ºF or Lower

140ºF

23ºF

122ºF

40ºF

108ºF

64ºF or Higher

86ºF