Setting The Boiler Parameters

Parameter mode

To access PARAMETER mode when the sys-
tem is in STANDBY mode, press the MODE
button once.

To scroll through the list of parameters, simply
press the “STEP” button. The first digit is the
parameter number followed by the parameter
value. To modify a parameter value, use the +
or - keys. Then press “STORE” to save the
value you just changed. The display flashes
once to confirm the data has been stored.

To activate the parameters you changed, press
RESET. However, if you do not press a key, the
system returns to STANDBY mode after 20
minutes and automatically stores the changes.

Note 1: This parameter is factory set to 140ºF.
It is important to note the control adds 46ºF to
this setting, therefore the actual domestic hot
water setting is 140ºF + 46ºF = 186ºF.

Note 2: This parameter should not be changed
from the factory setting of “01”. The perfor-
mance of the DHW will be affected and can
become unreliable.

Note 3: This parameter should not be changed
from the factory setting of “01”. The perfor-
mance of the CH (Central/Space Heating) will
be affected and can become unreliable.

ARA

P

ARA

P

MODE

NFO

I

MODE

Key:

Display

Pressing MODE once

Pressing MODE twice

Domestic Hot Water Setting (See Note 1)

Domestic Hot Water Setup (See Note 2)

Space Heating Mode (See Note 3)

Maximum temperature in space heating

(CH) mode. In applications using an

outdoor sensor, this is the boiler outlet

target temperature at an outdoor

temperature of 0 F or below.

1.
2

1

4

0

0

1

0

1

8

1 0

3

4

.
.

.

.

STEP

STEP

STEP

STEP

Key: Display

Description of parameters

ARA

P

MODE

Key: Display

Pressing MODE once

Start-Up Procedures