3

Table 2. Roof Curb Mounting to Building Structure

BHRE Size

Curb Cab

Roof Curb

Minimum Fasteners

Outside

Flange

Roof

Opening

Steel Anchoring Concrete Anchoring

Timber Anchoring

105

20 x 20

(508 x 508)

18 1/2 x 18 1/2

(470 x 470)

3

3

3

22 1/2 x 22 1/2

(571 x 571)

13 1/2 x 13 1/2

(343 x 343)

122

23 x 23

(584 x 584)

21 1/2 x 21 1/2

(546 x 546)

3

3

3

25 1/2 x 25 1/2

(648 x 648)

16 1/2 x 16 1/2

(419 x 419)

135

25 x 25

(635 x 635)

23 1/2 x 23 1/2

(597 x 597)

3

3

3

27 1/2 x 27 1/2

(698 x 698)

18 1/2 x 18 1/2

(470 x 470)

150

27 1/2 x 27 1/2

(698 x 698)

26 x 26

(660 x 660)

3

3

3

30 x 30 (762 x

762)

21 x 21

(533 x 533)

165

29 x 29

(737 x 737)

27 1/2 x 27 1/2

(698 x 698)

3

3

3

31 1/2 x 31 1/2

(800 x 800)

22 1/2 x 22 1/2

(571 x 571)

182

31 1/2 x 31 1/2

(800 x 800)

30 x 30

(762 x 762)

3

3

4

34 x 34 (864 x

864)

25 x 25

(635 x 635)

200

34 x 34

(864 x 864)

32 1/2 x 32 1/2

(825 x 825)

3

3

4

36 1/2 x 36 1/2

(927 x 927)

27 1/2 x 27 1/2

(698 x 698)

222

38 x 38

(965 x 965)

36 1/2 x 36 1/2

(927 x 927)

3

4

5

40 1/2 x 40 1/2

(1029 x 1029)

31 1/2 x 31 1/2

(800 x 800)

245

41 1/2 x 41 1/2

(1054 x 1054)

40 x 40

(1016 x 1016)

4

4

5

44 x 44 (1118 x

1118)

35 x 35

(889 x 889)

1.00

Roof Opening

[3/4" (19 mm) per side]

Outside of Roof Curb

1 1/2" (38 mm)

less than Fan Curb

2" (51 mm) Min. Embedment

(203 - 457 mm)

Curb Height

8" - 18"

[3/4" (19 mm) per side]

Outside of Roof Curb

1 1/2" (38 mm)

less than Fan Curb

(203 - 457 mm)

Curb Height

8" - 18"

1-1/2" (38 mm) Min. Embedment

Roof Opening

Center fasteners

(203 - 457 mm)

Curb Height

8" - 18"

[3/4" (19 mm) per side]

Outside of Roof Curb

1 1/2" (38 mm)

less than Fan Curb

Roof Opening

Outside Flange

Outside Flange

Outside Flange

2.00

Corner Detail Of

All Structures - Typ

2000 PSI Min. Concrete Strength

1/4" Dia. S.S. Hilti Kwik bolt expansion

anchors or equal.

4-1/2" (114 mm) min. spacing.

Located at each corner as shown.

Each side at center of unit.

Add additional fasteners to satisfy.

#10 Zinc plated wood screw or equal.

Located at each corner as shown.

Each side at center of unit.

3/4" (19 mm) min. spacing, 14-1/2" (368 mm) max. spacing.

Add additional fasteners to satisfy.

Wood Buck

Min. S.G. = .55

#12-14 Dril-flex self drilling screw or equal.

Located at each corner as shown.

Each side at center of unit.

3/4" (19 mm) min. spacing, 14-1/2" (368 mm) max. spacing.

Add additional fasteners to satisfy.

Min. 12 ga. or 1/8" (3 mm) thick steel member

Concrete Anchoring Instructions for Roof Curbs

Wood Anchoring Instructions for Roof Curbs

Steel Anchoring Instructions for Roof Curbs

Fig. 3

Figure 4.

Advertising