background image

3

Twin City IM-4300

4. Belt tension is adjusted at the factory. It should be

readjusted after a break-in period of 24 hours of

actual operation.

5. To adjust belt tension, loosen the hex head screw in

the tab of the motor plate. Snug belts by pulling on

the motor until the belt is tight. Tension is correct if

the belt can be twisted from

1

4

to

1

2

turn with mod-

erate pressure at a point midway between sheaves.

6. Belt condition and tension should be checked every

3 to 6 months depending on service. If belt tension

is too tight, there is a possibility of overloading the

motor as well as causing undue belt wear. If the belt

tension is too slack, then the wheel will fall off in

RPM, air delivery will decrease and the belts will wear

quite rapidly.

Figure 2. Opening Location of Duct Adapter Accessory

Figure 1. Typical Installation

X

L

Y

W

Duct

(Customer

Supplied)

Damper*

Duct Flange

By Customer

Duct Adapter

(Align this side with

inlet side of curb)

Apply foam tape to seal duct

to unit to prevent leakage

Roof

Curb

Nailer

Strip

Position duct adapter as shown and secure to nailer strip

with nails in holes provided in duct adapter.

*For a standard gravity (spring return) damper, recess the

damper a minimum of 2" inside the duct in order to clear the

fan outlet. For an optional motorized damper, the damper must

be recessed 12" to allow for clearance between the actuator

and fan outlet.

MODEL

DIMENSION (IN.)

BCFS

W

L

X

Y

140A

8

1

2

19

1

2

2

1

4

7

180A

10

1

2

22

1

2

1

7

8

9

240A

13

11

16

29

1

2

1

3

4

11

1

2

7. If the air handled by the unit is dust or grease laden,

a regular inspection and cleaning of the backdraft

damper and the wheel will ensure smooth, efficient

operation.

WARNING: Do not replace motor sheave with one larger

in diameter. Do not replace fan sheave with one smaller

in diameter. The sheave ratios are set so that the motor

will not be overloaded within the range of the adjust-

able sheave.
CHECK: Belt tension is adjusted at the factory, but it

should be readjusted after a break-in period of approxi-

mately 24 hours of actual operation.

Figure 3. Location of Fan Outlet

L

Fan Outlet

W

Y

X

Curb

Sq.

Inlet Side of Fan (Provide a min. of 15"
between inlet side and nearest obstruction)

Top View of Roof Curb Showing Duct Location

DIMENSIONS ARE NOT TO BE USED FOR CONSTRUCTION.

MODEL

DIMENSION (IN.)

CURB

SUPPLY

BCFS

W

L

X

Y

SQ.

DAMPER

140A

8

19 2

1

2

7

1

4

30 x 30

8 x 19

180A

10

22 2

1

8

9

1

4

36 x 36

10 x 22

240A

13

3

16

29

2

11

3

4

47 x 47

13 x 29