Backdraft Damper Installation (Optional - GRV, TEL, TIL)

1. Damper must be mounted prior to unit installation.
3. Damper should be installed inside curb on a nailing

strip or tray (see Figure 3).

4. Be sure knockout for power supply, in one corner of

the damper frame, is in the most convenient position

for connecting between power source and conduit

raceway of unit.

5. Before setting unit on curb, ascertain that the damper

is positioned horizontally and operative.

6. Damper motors (optional) are available for 115, or

208-230, 460V, or 575V. When power supply is three-

phase, the damper can be connected across any two

of the three phases. A power supply of 575V requires

a step-down transformer to 115V. Damper motor is

energized continuously when open.

NOTE: Outside dimensions of damper are

1

8

" less than

specified.
CAUTION: Installation of the damper will differ when

using the unit as a relief ventilator versus an intake. The

damper must be motorized when used with a GRV as

an intake ventilator.

1. Periodically inspect bird or insect screens to ensure

they are clean and not restricting airflow.

2. If using a backdraft damper on a GRV, TEL or TIL

Ventilator, ensure that it can operate freely.

3. Make sure the butterfly dampers on an LUG operate

freely.

4. Periodically inspect filters on a TIL, if so equipped,

to ensure they are clean.

Seller warrants to the original purchaser that the goods

sold hereunder shall be free from defects in workman-

ship and material under normal use and service (except

in those cases where the materials are supplied by the

buyer) for a period of one year from the date of original

installation or eighteen (18) months from the date of

shipment, whichever occurs first. The liability of seller

under this warranty is limited to replacing, repairing, or

issuing credit (at cost, F.O.B. factory and at seller’s

discretion) for any part or parts which are returned by

buyer during such period provided that:
a. seller is notified in writing within ten (10) days fol-

lowing discovery of such defects by buyer, or within

ten (10) days after such defects should reasonably

have been discovered, whichever is less;

b. the defective unit is returned to seller, transportation

charges prepaid by buyer.

c. payment in full has been received by seller for said

products; and

d. seller’s examination of such unit shall disclose to its

satisfaction that such defects have not been caused

by misuse, neglect, improper installation, repair,

alteration, act of God, or accident.

No warranty made hereunder shall extend to any seller

product whose serial number is altered, effaced or

removed. Seller makes no warranty, express or implied,

with respect to motors, switches, controls, or other

components of seller’s product, where such components

are warranted separately by their respective manufac-

turers. THIS WARRANTY IS EXPRESSLY IN LIEU OF

ALL OTHER WARRANTIES, EXPRESS OR IMPLIED,

WHETHER STATUTORY OR OTHERWISE, INCLUDING

ANY IMPLIED WARRANTY OF MERCHANTABILITY OR

FITNESS FOR A PARTICULAR PURPOSE. In no event

shall seller be liable to buyer for indirect, inciden-

tal collateral, or consequential damages of any kind.

(BUYER’S FAILURE TO PAY THE FULL AMOUNT DUE

WITHIN SIXTY (60) DAYS OF DATE OF INVOICE SHALL

OPERATE TO RELEASE SELLER FROM ANY AND ALL

LIABILITY OR OBLIGATION ARISING PURSUANT TO

ANY WARRANTY, EXPRESS OR IMPLIED, WHETHER

STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED

WARRANTY OR MERCHANTABILITY OR FITNESS FOR

A PARTICULAR PURPOSE, MADE IN CONNECTION

WITH ANY CONTRACT FORMED HEREUNDER. BUYER

AGREES THAT SUCH FAILURE TO PAY SHALL

CONSTITUTE A VOLUNTARY WAIVER OF ANY AND ALL

SUCH WARRANTIES ARISING PURSUANT TO SUCH

CONTACT.)

Limitation of Warranties and Claims

Maintenance

TWIN CITY FAN & BLOWER | WWW.TCF.COM

5959 Trenton Lane N | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601

Figure 3. Backdraft Damper Installation

MOUNTING SCREW
(FIELD SUPPLIED)

KNOCKOUT FOR
POWER SUPPLY

ROOF CURB

BACKDRAFT DAMPER
(OPTIONAL)

DAMPER TRAY