Liquid propane gas connection – Twin Eagles TEBC30-B User Manual

Page 10

Advertising
background image

LIQUID PROPANE GAS CONNECTION

Notice
All gas installations, conversions, and/or adjustments must be performed by an authorized service agent.

Notice
If your Dine & Breakfast Club is for Liquid Propane application, a factory supplied L.P regulator is set for 11”
WC and is for use with L.P. gas only. The factory-supplied regulator and hose must be used with a 20 lb.
L.P. cylinder. For plumb-in installation (system L.P. installation), the regulator must be changed and a main
gas shutoff valve must be installed. Contact your Twin Eagles dealer for a system L.P. regulator.

Warning
The gas supply hose should be inspected prior to each use. Do not use a gas hose that has abrasions, cuts,
or excessive wear.

The gas supply must be turned off at the LP Gas supply cylinder and the LP Gas supply cylinder must be
disconnected from the regulator when this outdoor cooking gas appliance is not in use.

When your Dine & Breakfast Club is stored indoors, remove and store the LP Gas cylinder outdoors in a
protected, cool, and dry location out of reach of children. The cylinder should not be stored in a building,
garage, or any other enclosed area.

Caution
Store the cylinder in an upright position so that the cylinder valve is at the top. This will ensure proper vapor
withdrawal.

The cylinder used must include a collar to protect the cylinder valve.

Store any spare or extra gas cylinder(s) in a cool, well ventilated outdoor location at least 15 feet from the Dine
& Breakfast Club, other open flame, heat-producing appliance(s) or heat source.

NOTE: An enclosure for a propane gas cylinder shall be vented by openings on the level of the cylinder valve
and at floor level. The effectiveness of the opening(s) for purposes of ventilation shall be determined with the
propane gas supply cylinder in place. This shall be accomplished by one of the following:

a. One side of the enclosure shall be completely open; or,
b. For an enclosure having four sides, a top and a bottom:

一 At least two ventilation openings at cylinder valve level shall be provided in the sidewall, equally sized,
spaced at 180 degrees (3.14 rad), and unobstructed. Each opening shall have a total free area of not less
than ½ square inch per pound (7.1cm²/kg) of stored fuel capacity and not less than a total free area of 10
square inches (64 cm²).
一 Ventilation opening(s) shall be provided at floor level and shall have total free area of not less than ½
square inch per pound (7.1 cm²/kg) of stored fuel capacity and not less than a total free area of 10 square
inches (64.5 cm²). If ventilation openings shall be at floor level and are in a sidewall, there shall be at least
two openings. The bottom of the openings shall be at floor level and the upper edge no more than 5 inches
(127 mm) above the floor. The openings shall be equally sized, spaced at 180 degrees (3.14 rad) and
unobstructed.

c. Every opening shall have minimum dimensions so as to permit the entrance of 1/8 inch (3.2 mm) diameter

rod.

5

Advertising