Vtr8300 series, User interface guide – Viconics VTR8300 Line Voltage User Interface Guide User Manual
Page 5

VTR8300 Series
5
User Interface Guide
Viconics Technologies Inc.
I Small Building Systems I 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I www.viconics.com
028-6045-01
April 2014
© 2
01
4 V
ic
on
ic
s T
ec
hn
ol
og
ie
s. A
ll r
ig
ht
s r
es
er
ve
d
.
Configuration parameters
default value
Significance and adjustments
ZigBee
®
channel
Channel selection
Default value = 10
Range is: 10 to 25
This parameter (Channel) is used to link specific Terminal Equipment
Controllers to specific ZigBee
®
coordinators. For every Terminal Equipment
Controller reporting to a coordinator, be sure you set the SAME channel
value both on the coordinator and the Terminal Equipment Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of available
channel is from 11 to 25.
ZigBee
®
status
( read only )
( Not Det ): ZigBee
®
module not detected
( Pwr On ): ZigBee
®
module detected but not configured
( No NWK ): ZigBee
®
configured but no network joined
( Joined ): ZigBee
®
network joined
( Online ): Communicating
PARAMETER DETAILS (CONT'D)