Remote sensor accessories – Viconics VT7600 Installation Guide (First Release 1000 Series) User Manual
Page 6

6
AU
D1
RS
Scom
C
D2
Scom
RS
Scom
RS
C
DI
Aux
Scom
RS
Scom
RS
Scom
RS
Scom
RS
VT7600 Series
Thermostat
2x S3010W1000 and 1x S3020W1000
Remote wiring 3 sensors
S2-1 = OFF / S2-2 = OFF
AU
D1
RS
Scom
C
D2
Scom
RS
Scom
RS
C
DI
Aux
Scom
RS
Scom
RS
Scom
RS
Scom
RS
C
DI
Aux
VT7600 Series
Thermostat
1x S3010W1000 and 2x S3020W1000
Remote wiring 3 sensors
S2-1 = OFF / S2-2 = OFF
Remote sensor accessories
Model no.
Description
S3010W1000
Wall mounted temperature sensor
S3020W1000
Wall mounted temperature sensor with override button and occupancy status LED
S2020E1000
Outdoor temperature sensor
S2060A1000
Averaging temperature sensor
S2000D1000
Duct mounted temperature sensor
Remote mount temperature sensors use 10K NTC thermistors.
• This sensor can be used for:
• 3 thermistors with 2 dip switches are provided with each sensor for various
averaging combinations
• Optional occupancy led
• Optional override key
Fig.8 – S3020W1000
wall mounted sensor
Wiring example of single remote room sensor:
Wiring examples of 2 remote room sensors for averaging applications:
Wiring examples of 3 remote room sensors for averaging applications:
Notes for averaging applications:
•
S3010W1000 and S3020W1000 can be
mixed matched.
•
S3010W1000 and S3020W1000 are to
be wired in parallel.
•
Respect the dip switch setting in each
remote sensor.
AU
D1
RS
Scom
C
D2
Scom
RS
Scom
RS
C
DI
Aux
Scom
RS
Scom
RS
OR
AU
D1
RS
Scom
C
D2
Scom
RS
Scom
RS
C
DI
Aux
Scom
RS
Scom
RS
C
DI
Aux
AU
D1
RS
Scom
C
D2
Scom
RS
Scom
RS
Scom
RS
Scom
RS
C
DI
Aux
VT7600 Series
Thermostat
1x S3020W1000
Remote wiring 1 sensor
S2-1 = ON / S2-2 = ON
S3010W1000
Remote wiring 1 sensor
S2-1 = ON / S2-2 = ON
VT7600 Series
Thermostat
2x S3020W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
AU
D1
RS
Scom
C
D2
Scom
RS
Scom
RS
Scom
RS
Scom
RS
2x S3010W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
VT7600 Series
Thermostat
VT7600 Series
Thermostat
1x S3010W1000 and 1x S3020W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
1 2
ON
Dip switch
setting for:
1 sensor
S2-1 = ON
S2-2 = ON
1 2
ON
Dip switch
setting for:
2 sensors
S2-1 = OFF
S2-2 = ON
1 2
ON
Dip switch
setting for:
3 sensors
S2-1 = OFF
S2-2 = OFF