10 | PIR Ready VT7600 Series-Installation Guide

Outdoor air temperature

 Outdoor air temperature display is only enabled when outdoor air temperature sensor is

connected.

A maximum range status display of 50 °C (122 °F) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.

A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts and
economizer function are automatically disabled.


Alarms

If alarms are detected, they will automatically be displayed at the end of the status
display scroll.

During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.

Two alarms maximum can appear at any given time.

The priority for the alarms is as follows:


Sequence of manual-scroll status display:
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively. The
last item viewed will be shown on the display for 30 seconds before returning to automatic
scrolling. Temperature is automatically updated when scrolling is held.

Clock Status

System

Mode

Schedule

Status

Outdoor

Temperature

Alarms

(if detected)

Monday

Sys Mode

Occupied

Outdoor

Service

12:00 AM

Off

xx.x °C or °F

DAS Alrm

Sys Mode

Unoccupied

SetClock

Auto

Filter

Sys Mode

Cool

Override

Fan lock

Frost ON

Sys Mode

Heat

Frost ON

Indicates that the heating is energized by the low limit frost protection room
temperature setpoint 5.6 °C (42 °F)

SetClock

Indicates that the clock needs to be reset. There has been a power failure
which has lasted longer than 6 hours

Service

Indicates that there is a service alarm as per one of the configurable digital
input (DI1 or DI2)

Filter

Indicates that the filters are dirty as per one of the configurable digital input
(DI1 or DI2)

Fan lock

Indicates that the heating and cooling action are locked out due to a defective
fan operation

DAS

Alarm

Indicates that the discharge air temperature is either too low or too high.