Pband
Proportional band setting
Default is : 3
Adjust the proportional band used by the Terminal Equipment
Controller PI control loop.
Note that the default value of 3.0 °F (1.2 °C) gives
satisfactory operation in most normal installation cases. The
use of a proportional band different than the factory one is
normally warranted in applications where the Terminal
Equipment Controller location is problematic and leads to
unwanted cycling of the unit. A typical example is a wall
mounted unit where the Terminal Equipment Controller is
installed between the return and supply air feeds and is
directly influenced by the supply air stream of the unit.
VALUE
°
F SCALE PBAND
°
C SCALE
PBAND
3
3 F
1.2 C
4
4 F
1.7 C
5
5 F
2.2 C
6
6 F
2.8 C
7
7 F
3.3 C
8
8 F
3.9 C
9
9 F
5.0 C
10
10 F
5.6 C