Viconics VTR7300 Application Manual User Manual

Page 15

Advertising
background image

15

Wiring of Local Inputs to VTR73xxA Terminal Equipment Controller

Wiring of Remote Inputs to VC3504E & 3404E Relay Packs



VTR73xxA

Terminal Controller

13 - BI 1

14 - Scom

15 - BI 2

Local BI 1 Input by configuration:
- None ( monitoring only
)- Remote motion detector: Motion NO or Motion
NC

- Remote Night Setback:
R

NSB

- Window contact: Window

Local BI 2 Input by configuration:
- None ( monitoring only
)- Door contact: DoorDry

VC30x04E

Relay Pack

OR

4 - RUI1

5 - Scom

6 - RBI2

7 - SS

8 - RS

Remote RUI 1 Input by configuration:
- None ( monitoring only )
- Local changeover sensor ( 10K type2 COS )
- Local changeover contact ( COC NO or COC NC )

- Service alarm ( Service )
- Filter Alarm ( Filter )

Remote RBI 2 Input by configuration:
- None ( monitoring only )
- Service alarm ( Service )
- Filter Alarm ( Filter )

SS Supply sensor:
-

10K type2

monitoring only

- Auto dectected

RS Return Air Sensor:
-

10K type2

main temperature copntrol
i

- Auto dectected ( by-passes VTR73xxA internal sensor )